Technical Handbook 105
Only for charge cycles: energy transferred to the plant battery
during BULK phase (Ah).
2
Only for charge cycles: energy transferred to the plant battery
during ABSORBTION phase (Ah).
2
Only for charge cycles: energy transferred to the plant battery
during FLOAT phase (Ah).
2
Only for charge cycles: total energy transferred to the plant
battery during the cycle (Wh).
2
The most recent record is associated to the highest number. Use the ▲ and ▼ buttons to
scroll cyclically trough all recordings.
Using the ◄ and ► buttons, you can browse through the pages related to the record.
To display every record, the controller uses one/two pages of the display.
The main page has the following format:
The second line of each page shows what record is currently displayed (7) and the number of
records stored (8). Once the total number of records available is reached, the second value
will remain fixed at the limit value (31) up to a possible log resetting. The example in the
previous figure shows record 7 of 8 stored (out of 31 available).
The fourth line of each event page displays the kind of cycle.
When previously configured events occur, the controller adds a record in this archive. Full
capacity is 126 records. If the archive is full and a new event occurs, the less recent is
overwritten (so always the last 126 events are stored). For each event, the controller stores:
•
A numerical code identifying it.
•
The date/time of the event.
•
The operating mode of the controller.
•
The engine status.
•
The generator status.
•
The status of all circuit breakers.
•
The status of the digital inputs (of the controller, of the expansion modules and
virtual).
•
The first four anomalies (if present).
•
The plant battery voltage (Vdc).
•
The plant battery current (Adc).
•
The plant battery charge level (Ah).
If the event is an anomaly, measures described for the analogue archives are also stored.
Configuring the events to be recorded is possible with parameter P.0441 (managed by bits):
Bit Value Hexadecimal Description
0
1
0001
Board operating mode
1
2
0002
Auxiliary source status
2
4
0004
Generator status
3
8
0008
Engine status
H.09 HISTORY LOGS |
1 CHARGE CYCLES 07/08
Charge cycle
08/03/17 16:27:43
24.9 Vdc 245 Ah
08/03/17 16:56:57
27.1 Vdc 330 Ah