Technical Handbook 25
Terminal
Function
JN-1
DIF.3001
– “Status of GCB circuit breaker”
JN-2
DIF.3011
– “Trip of GCB circuit breaker”
JN-3
DIF.3006
– “Status of BCB circuit breaker”
JN-4
DIF.3016
– “Trip of BCB circuit breaker”
JN-5
DIF.3007
– “Status of LCB circuit breaker”
JN-6
DIF.3017
– “Trip of LCB circuit breaker”
JN-7
DIF.0000
– “Not used”
JN-8
DIF.2501
– “Inhibition of start”
JT-1
DIF.0000
– “Not used
JT-2
DIF.0000
– “Not used
JT-3
DIF.0000
– “Not used
JT-4
DIF.0000
– “Not used
The following functions, not directly linked to the operation sequences of the controller, are
selectable for any digital output:
•
DIF.0101 -
“Used by PLC”. It is possible to use the digital inputs of the controller only
for the PLC logics, without the controller normal operation sequence using them. In
these cases, it is possible to leave the inputs configured with the function DIF.0000
(
“Not used”). Therefore, there’s the risk to reuse the input for other purposes, as it
seems to be available: for this reason, there is the DIF.0101 function (to indicate the
input used, even if not directly by the controller).