194
Technical Handbook
It is activated after P.0438 days since parameter P.0438 was last set (the check is done at
each hour change). It cannot be cancelled even disconnecting the controller's power supply.
It can be cancelled only by setting P.0438 again, setting it to zero to disable the function or
confirming the actual value or setting a new one.
Hours are counted even when engine is stopped
Type:
Warning
Related parameters:
P.4009
Function of the analogue input 2 (JQ) or equivalent for the other
inputs.
P.0216
Time mask for engine protections.
P.0373
High oil temperature threshold.
P.0374
High oil temperature delay.
P.0700
Engine type.
To disable:
P.0374 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled if the controller acquires the measurement of the oil temperature
(directly from the ECU of the engine or if one of the analogue inputs of the controller is
configured to acquire such measure - function AIF.1100 or AIF.1101 in parameter P.4009 or
equivalent for the other inputs) and if a time other than zero has been set for the protection
(parameter P.0374). It is only enabled if the engine has been started by the controller (if the
command for the fuel solenoid is activated) and is disabled in the engine start/stop phases. It
is activated if the oil temperature remains continuously above or equal to threshold P.0373 for
time P.0374, but only after the time P.0216 (oil mask) from engine start has elapsed (this is to
allow you to start the engine idle, to cool it off).
Type:
Warning
Related parameters:
P.0102
Nominal voltage (AC) of the generator.
P.9641
Nominal voltage (DC).
P.0202
Hysteresis for generator's measures.
P.0391
Low voltage threshold.
P.0392
Low voltage delay.
To disable:
P.0392 = 0
Enabled in:
*
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection, when possible, works on the DC voltage of the generator. If not possible (GCB
closed), if AC voltages are available it works with them,
otherwise it will never be activated
.
It is only enabled if the engine has been started by the controller (if the command for the fuel
solenoid is activated) and it is disabled during the crank/stop cycles. It is enabled the first time
(from engine start) the generator's voltages and frequency/speed enter the tolerance range
(see generator sequence description). In MAN it is only enabled if the GCB breaker is closed.
It is activated if, under the conditions previously mentioned, the DC voltage of the generator
or at least one of the AC voltages is continuously below the threshold P.0391 for the time
P.0392.
In MAN it is only enabled if the GCB breaker is closed, or if the bit 2 of the parameter P.0249
is set to
“1”.
Type:
Warning
Related parameters:
P.0418
Test enable days.
P.0420
Test duration.