The connection to the AC generator lines is optional; if required, it is made through the
connector JG of the controller.
Tri-phase connection:
Parameter
Value
Description
P.9613
025-AC voltage for the generator (L1)
Connect phase L1 (or R) to
terminal JG-3
P.9612
026-AC voltage for the generator (L2)
Connect phase L2 (or S) to
terminal JG-2
P.9611
027-AC voltage for the generator (L3)
Connect phase L3 (or T) to
terminal JG-1
P.9614
028-AC voltage for the generator (N)
Connect neutral (N) (if any) to
terminal JG-4
If the neutral is not present, the terminal JG-4 cannot be used for other functions.
Single-phase connection:
Parameter
Value
Description
P.9613
025-AC voltage for the generator (L1)
Connect phase L1 (or R) to
terminal JG-3
P.9614
028-AC voltage for the generator (N)
Connect
neutral
(N)
to
terminal JG-4
Terminals JG-1 and JG-2 can be used for other functions.