Engine Rated Power (SAE J1939: SPN166).
•
Engine Total Hours of Operation (SAE J1939: SPN247).
•
Key switch Battery Potential (SAE J1939: SPN158).
•
Engine Throttle Position (SAE J1939: SPN51).
•
Error code sent by the ECU with proprietary messages.
These pages are used to show the generic measurements acquired by analogue inputs
configured with the following functions:
•
AIF.2001: page E.11
•
AIF.2003: page E.12
•
AIF.2005: page E.13
The controller uses one row per each measure: on the left a description is shown (configured
by means the parameters related to the analogue input) and on the right the acquired measure,
eventually converted by means a conversion curve. If the page contains more than seven
measures, the controller shows all them by rotation (every 2 seconds, keep pressed the SHIFT
button to stop the rotation).
These pages are hidden if there are no measures to be shown.
This page is related to the hour / day counters for the genset maintenance. It shows the
remaining hours to the next maintenance planned by parameters P.0424 and P.0437, and the
remaining days for the maintenance planned by parameter P.0438. If some of these
parameters are set to zero (maintenance not planned), the related counters are replaced by
dashes.
These acronyms are used below:
•
DPF - Diesel Particulate Filter
•
DOC - Diesel Oxidation Catalyst
•
SCR - Selective Catalyst Reduction
•
DEF - Diesel Exhaust Fluid
•
EST - Exhaust System Temperature
From version 1.05, the controller fully supports the TIER4 (US) and STAGE V (EU) directives
concerning generators emissions. This support consists of two parts:
•
Visualization. A minimum of measurements is required:
o
Percent of soot in the Diesel Particulate Filter (DPF).
o
Percentage of ash in the Diesel Particulate Filter (DPF).
o
Diesel Emissions Fluid (DEF) level.
The controller supports the following measurements, and displays them on this page:
o
DPF:
▪
spn 4781: “DPF Soot Mass”.
▪
spn 3719: “DPF Soot Load Percent”.
▪
spn 3720: “DPF Ash Load Percent”.
▪
spn 3721: “DPF Time Since Last Active Regeneration”.
▪
spn 3242: “DPF Intake Gas Temperature”.
▪
spn 3246: “DPF Outlet Gas Temperature”.
▪
spn 3251: “DPF Differential Pressure”.
o
DOC:
▪
spn 4765: “DOC Intake Gas Temperature”.
▪
spn 4766: “DOC Outlet Gas Temperature”.