Install a Fan Module
a.
Ensure the cables are free from binding and pinching.
b.
Slide the server into the rack until it locks into place.
8.
If you performed a cold-service procedure, power on the server.
Fan Module Reference
The six fan modules are located at the front of the chassis and provide cooling for the three
motherboard cooling zones (for more information, see
“Cooling Subsystem” on page 25
fans are hot-serviceable and accessible by partially extending the server from the rack. You do
not have to remove the server cover to service the fan modules.
Caution -
Server shutdown or component damage due to over-temperature condition. Fan
modules provide system cooling. If a fan module fails, replace it as soon as possible. When
you remove one of the fans in the back row, you must replace it within 30 seconds to prevent
overheating of the server.
Note -
If a failed fan is replaced too quickly, the fan indicator might still show a fault even after
the new fan is installed. When replacing a faulty fan, wait for the fan indicator to turn off after
removing the old fan and before installing the new fan. This will only take a few seconds.
The functions of the fan module status indicators is described below.
Front and Back Panel Indicators for Fan Failure
One or more of the following indicators might light when a fan module fault is detected:
■
Front and back Service Action Required indicators. See
and
“Server Back Panel Features” on page 18
indicators.
■
Fan module Service Action Required indicator.
■
Over Temperature Warning indicator. This indicator might also light if a fan fault causes an
unacceptable increase in system operating temperature.
Fan Module Indicator
Next to each fan module slot are indicators that are visible from the top of the server.
Servicing CRU Components
135
Содержание X5-4
Страница 1: ...Oracle Server X5 4 Service Manual Part No E56396 03 December 2015 ...
Страница 2: ......
Страница 10: ...10 Oracle Server X5 4 Service Manual December 2015 ...
Страница 14: ...14 Oracle Server X5 4 Service Manual December 2015 ...
Страница 21: ...Server Subsystems Overview Two CPU Block Diagram Oracle Server X5 4 Overview 21 ...
Страница 36: ...36 Oracle Server X5 4 Service Manual December 2015 ...
Страница 68: ...68 Oracle Server X5 4 Service Manual December 2015 ...
Страница 178: ...178 Oracle Server X5 4 Service Manual December 2015 ...
Страница 272: ...272 Oracle Server X5 4 Service Manual December 2015 ...
Страница 281: ...About the BIOS Setup Utility Keywords Main DIMM Information Processor 0 DIMMs BIOS Setup Utility Menu Options 281 ...
Страница 293: ...About the BIOS Setup Utility Keywords Memory Configuration Numa Patrol Scrub BIOS Setup Utility Menu Options 293 ...
Страница 307: ...About the BIOS Setup Utility Keywords Advanced Network Stack BIOS Setup Utility Menu Options 307 ...
Страница 327: ...About the BIOS Setup Utility Keywords IO Add In Cards Slot 1 Slot 11 BIOS Setup Utility Menu Options 327 ...
Страница 331: ...About the BIOS Setup Utility Keywords OSA Internal Support Disabled Enabled BIOS Setup Utility Menu Options 331 ...
Страница 340: ...340 Oracle Server X5 4 Service Manual December 2015 ...