![Omron CJ1W-MA - REV 10-2008 Скачать руководство пользователя страница 509](http://html1.mh-extra.com/html/omron/cj1w-ma-rev-10-2008/cj1w-ma-rev-10-2008_operation-manual_742343509.webp)
482
Error Reset
Section 12-6
12-6 Error Reset
The PCU indicates Unit common errors and individual axis errors in the Com-
mon Operating Memory Area and Axis Operating Input Memory Areas,
respectively, using Error Flags and error codes.
These errors can be cleared by removing the cause of the error and executing
ERROR RESET.
The methods for resetting Unit common errors and individual axis errors are
different.
12-6-1 Resetting Unit Common Errors
Unit common errors are cleared by turning ON (
) the UNIT ERROR RESET
Bit in the Common Operating Memory Area.
Reset Unit common errors when the Unit Busy Flag for the Position Control
Unit is OFF. If errors are reset when the Unit Busy Flag is ON, a multistart
error (Unit error code: 0021) will occur and it will not be possible to reset Unit
common errors.
When clearing Unit common errors, make sure that the UNIT ERROR RESET
Bit in the Common Operating Memory Area remains ON until the Unit Busy
Flag turns ON.
Common Operating Memory Area (Output)
n = CIO 1500 + (unit number
×
25)
Common Operating Memory Area (Input)
n = CIO 1500 + (unit number
×
25)
Timing Chart Example for UNIT ERROR RESET
Name
Word
Bit
Contents
UNIT ERROR
RESET Bit
n
00
: Resets Unit common error
Name
Word
Bit
Contents
Unit Error Flag
n+15
12
0: Unit common error has not occurred.
1: Unit common error has occurred.
Unit Busy Flag
n+16
14
0: PCU is not busy
1: PCU is busy
Unit error code
n+21
---
Stores the error code when a Unit common
error occurs.
UNIT ERROR RESET Bit
(word n, bit 00)
Unit Error Flag
(word n+15, bit 12)
Unit Busy Flag
(word n+16, bit 14)
Unit Error Code
(word n +21)
0000
0021 hex
0000
(Example) Multistart Error
n = CIO 1500 + (unit number
×
25)
The Unit Busy Flag remains ON
for at least one cycle time when
UNIT ERROR RESET is
executed.
Содержание CJ1W-MA - REV 10-2008
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 21: ...xxii ...
Страница 57: ...30 Starting Operation Section 2 2 ...
Страница 97: ...70 Wiring Section 3 4 ...
Страница 247: ...220 Transferring Servo Parameters Section 5 3 ...
Страница 281: ...254 Standard Settings for Servo Drives Using MECHATROLINK Section 6 4 ...
Страница 343: ...316 Absolute Encoder Origin Section 8 6 ...
Страница 375: ...348 Linear Interpolation Section 9 7 ...
Страница 423: ...396 DEVIATION COUNTER RESET Section 10 10 ...
Страница 631: ...604 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Страница 641: ...614 Index ...
Страница 643: ...616 Revision History ...