![Omron CJ1W-MA - REV 10-2008 Скачать руководство пользователя страница 395](http://html1.mh-extra.com/html/omron/cj1w-ma-rev-10-2008/cj1w-ma-rev-10-2008_operation-manual_742343395.webp)
368
Speed Control
Section 10-5
The Receiving Command Flag turns ON for at least one cycle time when the
command to start speed control is received by the PCU. Use the Receiving
Command Flag when starting and changing option commands to control the
ON/OFF timing for SPEED CONTROL.
During speed control, bits 07 and 08 in the Servo Status Flags (word b+1) of
the Axis Operating Input Memory Area function as the Speed Conformity Flag
and Zero Speed Flag respectively.
The command present position that is output during speed control is calcu-
lated from the feedback position and the position deviation that is inferred
from the current speed.
Acceleration and Deceleration during Speed Control
When SPEED CONTROL is executed, the Servo Drive performs stepped
speed control from the present feedback speed to the target speed specified
in the speed command value for speed control. Apart from smoothly increas-
ing/decreasing the speed command value (for speed control) when starting
speed control, shock in acceleration/deceleration when performing speed
control can also be minimized by setting the Servo Parameters
Soft Start
Acceleration Time
and
Soft Start Deceleration Time
to create a trapezoidal
speed curve.
G-series Acceleration/Deceleration Constants for Speed Control
W-series Acceleration/Deceleration Constants for Speed Control
The
Soft Start Acceleration Time
and
Soft Start Deceleration Time
are set
respectively as the acceleration time and deceleration time between speed 0
(speed command value for speed control: 0%) and the momentary maximum
rotation speed of the Servomotor (speed command value for speed control:
100%).
The acceleration time and deceleration time for the actual target speed are as
follows:
Type
Parameter
No.
Parameter name
Unit
Setting
range
Data
length
Default
setting
---
Pn058
Soft start acceleration time
2 ms
0 to 5000
2
0
---
Pn059
Soft start deceleration time
2 ms
0 to 5000
2
0
Type
Parameter
No.
Parameter name
Unit
Setting
range
Data
length
Default
setting
---
Pn305
Soft start acceleration time
ms
0 to 10000
2
0
---
Pn306
Soft start deceleration time
ms
0 to 10000
2
0
Pn305
0
Actual acceleration time
Servomotor speed
+r/min
Actual deceleration time
Time
Pn306
Actual acceleration (deceleration) time =
×
Soft start acceleration (deceleration) time
Speed command value for speed control (r/min)
Momentary maximum rotation speed (r/min)
Momentary maximum
rotation speed (See note.)
Speed command value for
speed control
Содержание CJ1W-MA - REV 10-2008
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 21: ...xxii ...
Страница 57: ...30 Starting Operation Section 2 2 ...
Страница 97: ...70 Wiring Section 3 4 ...
Страница 247: ...220 Transferring Servo Parameters Section 5 3 ...
Страница 281: ...254 Standard Settings for Servo Drives Using MECHATROLINK Section 6 4 ...
Страница 343: ...316 Absolute Encoder Origin Section 8 6 ...
Страница 375: ...348 Linear Interpolation Section 9 7 ...
Страница 423: ...396 DEVIATION COUNTER RESET Section 10 10 ...
Страница 631: ...604 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Страница 641: ...614 Index ...
Страница 643: ...616 Revision History ...