![Omron CJ1W-MA - REV 10-2008 Скачать руководство пользователя страница 368](http://html1.mh-extra.com/html/omron/cj1w-ma-rev-10-2008/cj1w-ma-rev-10-2008_operation-manual_742343368.webp)
341
Linear Interpolation
Section 9-7
Settings for Interpolation Axis Operations: Axis Operating Output
Memory Areas for Axes Designated by Interpolation Axis Designation
a = Beginning word of Axis Operating Output Areas specified in Common
Para (Axis No.
−
1)
×
25
The G-series Servo Drives do not support exponential curve designation fil-
ters. When using a G-series Servo Drive, do not attempt to use an exponential
curve designation filter.
The SMARTSTEP Junior Servo Drives do not support acceleration/decelera-
tion filters and torque limits. When using a SMARTSTEP Junior Servo Drive,
do not attempt to use an acceleration/deceleration curve designation or for-
ward/reverse torque limit designation.
Note
(1) For interpolation acceleration and deceleration time settings, the upper
and lower limits for axis acceleration and deceleration speeds are restrict-
ed to a range of 1 to 65,535 [
×
10,000 command units/s
2
]. If the acceler-
ation or deceleration speeds calculated from the linear interpolation
operation settings for an interpolation axis are extremely low or high, the
linear interpolation following may not be correct.
(2) The interpolation acceleration/deceleration times are converted using the
unit for the
Second-step Linear Acceleration Constant
for W-series Servo
Drives (Pn80B) or
Linear Acceleration Constant
for G-series Servo
Drives (Pn107) and
Second-step Linear Deceleration Constant
for W-se-
ries (Pn80E) or
Linear Deceleration Constant
for G-series Servo Drives
(Pn10A) (10,000 command units/s
2
). In operation, the actual acceleration
and deceleration times are thus affected by the precision of the command
unit.
Name
Word
Bits
Contents
G Series
W Series
SMART-
STEP
Junior
Position Command Value a+2
a+3
---
Position command value (rightmost word)
Position command value (leftmost word)
Unit: Command unit
Command range:
−
2,147,483,648 to
2,147,483,647 (80000000 hex to
7FFFFFFF hex)
The command value is limited by the
allowable positioning range.
(For details, refer to
9-4-1 Starting Direct
Operation
.)
Supported Supported Supported
Speed Command Value
(for Position Control)
a+4
a+5
---
Speed command value (rightmost word)
Speed command value (leftmost word)
Unit: Command units/s
Command range: 0 to 2,147,483,647
(00000000 hex to 7FFFFFFF hex)
For details on speeds for interpolation
operations, refer to
Linear Interpolation
Operation Speeds
on page 346.
Supported Supported Supported
Accelera-
tion/decel-
eration
curve des-
ignation
Exponen-
tial curve
designation
a+16
03
1:
Use exponential acceleration/decelera-
tion curve.
Not sup-
ported
Supported Not sup-
ported
S-curve
designation
04
1: Use S-curve acceleration/deceleration
curve.
Supported Supported Not sup-
ported
Forward rotation current
limit
14
1: Use forward torque limit.
Supported Supported Not sup-
ported
Reverse rotation current
limit
15
1: Use reverse torque limit.
Supported Supported Not sup-
ported
Содержание CJ1W-MA - REV 10-2008
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 21: ...xxii ...
Страница 57: ...30 Starting Operation Section 2 2 ...
Страница 97: ...70 Wiring Section 3 4 ...
Страница 247: ...220 Transferring Servo Parameters Section 5 3 ...
Страница 281: ...254 Standard Settings for Servo Drives Using MECHATROLINK Section 6 4 ...
Страница 343: ...316 Absolute Encoder Origin Section 8 6 ...
Страница 375: ...348 Linear Interpolation Section 9 7 ...
Страница 423: ...396 DEVIATION COUNTER RESET Section 10 10 ...
Страница 631: ...604 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Страница 641: ...614 Index ...
Страница 643: ...616 Revision History ...