460
Troubleshooting Procedure
Section 12-2
Timing Chart for Axis Errors and Warnings
Note
If an axis warning occurs (Warning Flag = 1), the PCUs’ command response
time will be delayed due to the warning processing. The PCU processing time
required from receiving a command from the CPU Unit until the command is
sent using MECHATROLINK communications is one MECHATROLINK com-
munications cycle if an axis warning has not occurred, and three MECHA-
TROLINK communications cycles if an axis warning has occurred. If the
machine's operation is affected by the PCU's command response time, clear
the axis warning status using ERROR RESET or disable the warnings using
the Servo Drive settings.
For details on the PCU's command response time, refer to
Command
Response Time
in
Appendix A Performance Characteristics
.
12-2 Troubleshooting Procedure
The basic flow of troubleshooting errors that occur in the PCU is as follows:
ERROR RESET Bit
(word a, bit 12)
Warning Flag
(word b, bit 11)
Error Flag
(word b, bit 12)
Busy Flag
(word b, bit 13)
Axis error code
(word b+4)
0000
4096 (Hex)
0000
4096 (Hex) 40E6 (Hex)
(Example)
Communications warning
Communications
warning
Communications
error
The Busy Flag remains ON for at
least one cycle time when ERROR
RESET is executed.
If the Error Flag turns ON while the
Warning Flag is already ON, the axis
error code will be overwritten.
a = Beginning word of Axis Operating Output Areas specified in Common Para (Axis No.
−
1)
×
25
b = Beginning word of Axis Operating Input Areas specified in Common Para (Axis No.
−
1)
×
25
PCU
Error occurs
Operation when
error occurs
Error Flag turns ON
Error code stored
ERROR RESET
executed
Recovery
Notification
ERROR
RESET
User application
Error evasion operation
in application (as
required)
Cause of error
investigated
Cause of error
isolated using PCU
display
Cause of error
determined using
error code
Countermeasure
determined according
to each error cause
Cause of error
removed
ERROR RESET
executed
12-3 LED Error Indicators
12-4 Error Codes
12-4 Error Codes
12-5 Troubleshooting
12-6 Error Reset
Содержание CJ1W-MA - REV 10-2008
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 21: ...xxii ...
Страница 57: ...30 Starting Operation Section 2 2 ...
Страница 97: ...70 Wiring Section 3 4 ...
Страница 247: ...220 Transferring Servo Parameters Section 5 3 ...
Страница 281: ...254 Standard Settings for Servo Drives Using MECHATROLINK Section 6 4 ...
Страница 343: ...316 Absolute Encoder Origin Section 8 6 ...
Страница 375: ...348 Linear Interpolation Section 9 7 ...
Страница 423: ...396 DEVIATION COUNTER RESET Section 10 10 ...
Страница 631: ...604 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Страница 641: ...614 Index ...
Страница 643: ...616 Revision History ...