![Omron CJ1W-MA - REV 10-2008 Скачать руководство пользователя страница 326](http://html1.mh-extra.com/html/omron/cj1w-ma-rev-10-2008/cj1w-ma-rev-10-2008_operation-manual_742343326.webp)
299
Origin Return
Section 8-4
Note
Execute ORIGIN RETURN when the origin has been established. If ORIGIN
RETURN is executed when the origin has not been established, a Present
Position Unknown Error (axis error code: 3030) will occur.
8-4-1
Origin Return Data Settings
A simple explanation of the main parameters and data used to execute ORI-
GIN RETURN is provided here. To execute ORIGIN RETURN, apart from the
parameters explained here, the following parameters also need to be set as
basic settings for operating the PCU.
For details on command units, refer to
7-2 Control Units
. The setting units for
parameters and data depend on the specified command unit.
Servo Parameter Area
Command Unit Parameters
The command unit default setting is pulses.
G-series Acceleration/Deceleration Constants
Model
Parameter
No.
Parameter name
Unit
Setting
range
Parameter
size
Default
setting
R88D-GN
@
-
ML2
Pn205
Electronic gear ratio G1 (numerator)
---
1 to
1073741824
4
1
Pn206
Electronic gear ratio G2 (denominator)
---
1 to
1073741824
4
1
R88D-WT
@
Pn202
Electronic gear ratio G1 (numerator)
---
1 to 65535
2
4
Pn203
Electronic gear ratio G2 (denominator)
---
1 to 65535
2
1
R88D-WN
@
-
ML2
Pn20E
Electronic gear ratio G1 (numerator)
---
1 to
1073741824
4
4
Pn210
Electronic gear ratio G2 (denominator)
---
1 to
1073741824
4
1
SMART-
STEP Junior
Pn20E
Electronic gear ratio G1 (numerator)
---
1 to
1073741824
4
1
Pn210
Electronic gear ratio G2 (denominator)
---
1 to
1073741824
4
1
Type
Parame-
ter No.
Parameter name
Unit
Setting
range
Parame-
ter size
Default
setting
Accel-
eration/
decel-
eration
con-
stants
Pn107
Linear acceleration constant
10,000
command
units/s
2
−
32768
to 32767
2
100
Pn10A
Linear deceleration constant
10,000
command
units/s
2
−
32768
to 32767
2
100
Accel-
eration/
decel-
eration
filters
Pn10E
Moving average time
0.1 ms
0 to 5100 2
0
Содержание CJ1W-MA - REV 10-2008
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 21: ...xxii ...
Страница 57: ...30 Starting Operation Section 2 2 ...
Страница 97: ...70 Wiring Section 3 4 ...
Страница 247: ...220 Transferring Servo Parameters Section 5 3 ...
Страница 281: ...254 Standard Settings for Servo Drives Using MECHATROLINK Section 6 4 ...
Страница 343: ...316 Absolute Encoder Origin Section 8 6 ...
Страница 375: ...348 Linear Interpolation Section 9 7 ...
Страница 423: ...396 DEVIATION COUNTER RESET Section 10 10 ...
Страница 631: ...604 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Страница 641: ...614 Index ...
Страница 643: ...616 Revision History ...