![Omron CJ1W-MA - REV 10-2008 Скачать руководство пользователя страница 496](http://html1.mh-extra.com/html/omron/cj1w-ma-rev-10-2008/cj1w-ma-rev-10-2008_operation-manual_742343496.webp)
469
Error Codes
Section 12-4
Individual Axis Errors
Indicator status
Category
Error
name
Error
code
Probable
cause
Clearing method
Operation
after error
RUN
ERC
ERH
ERM
MLK
M
E
C
H
A
T
R
O
LI
NK
com
m
unicat
ions
er
rors
Lit
Flash-
ing
Not lit
Lit
Unde-
ter-
mined
Communi-
cations
error
Synchro-
nous
communi-
cations
alarm
3010
MECHA-
TROLINK
communica-
tions cannot
be performed
correctly with
the corre-
sponding axis.
Check the connection of
the MECHATROLINK
communications cable.
After removing the
cause preventing com-
munications, such as
breaks or noise in the
connection, execute
CONNECT again.
Operation
stops
according
to the
method
used when
the Servo
Drive alarm
occurs.
(The PCU
executes
DECELER-
ATION
STOP.)
Operation
of the cor-
respond-
ing axis is
prohibited.
Communi-
cations
alarm
3011
MECHA-
TROLINK
communica-
tions cannot
be performed
correctly with
the corre-
sponding axis.
Check the connection of
the MECHATROLINK
communications cable.
After removing the
cause preventing com-
munications, such as
breaks or noise in the
connection, execute
CONNECT again.
Operation
stops
according
to the
method set
in the
Servo
Drive for
alarms.
(The PCU
executes
DECELER-
ATION
STOP.)
Operation
of the cor-
respond-
ing axis is
prohibited.
Com-
mand tim-
eout
3012
No MECHA-
TROLINK
communica-
tions
response has
been received
from the cor-
responding
axis.
When con-
nected to an
R88D-WN
@
-
ML2 Servo
Drive, this
error will occur
if a Servo
Parameter is
transferred
with an illegal
parameter
size.
After checking that no
error has occurred in the
MECHATROLINK device
connected to the corre-
sponding axis, execute
CONNECT again.
If this error occurs when
transferring a Servo
Parameter to the R88D-
WN
@
-ML2 Servo Drive,
check whether the Servo
Parameter is being
transferred with an ille-
gal parameter size.
Operation
stops
according
to the
method
used when
the Servo
Drive alarm
occurs.
(The PCU
executes
DECELER-
ATION
STOP.)
Operation
of the cor-
respond-
ing axis is
prohibited.
Содержание CJ1W-MA - REV 10-2008
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 21: ...xxii ...
Страница 57: ...30 Starting Operation Section 2 2 ...
Страница 97: ...70 Wiring Section 3 4 ...
Страница 247: ...220 Transferring Servo Parameters Section 5 3 ...
Страница 281: ...254 Standard Settings for Servo Drives Using MECHATROLINK Section 6 4 ...
Страница 343: ...316 Absolute Encoder Origin Section 8 6 ...
Страница 375: ...348 Linear Interpolation Section 9 7 ...
Страница 423: ...396 DEVIATION COUNTER RESET Section 10 10 ...
Страница 631: ...604 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Страница 641: ...614 Index ...
Страница 643: ...616 Revision History ...