217
Transferring Servo Parameters
Section 5-3
SAVE SERVO PARAMETER can be executed while the corresponding axis is
operating (Busy Flag ON). The following diagram shows the operation used to
save parameters to the W-series Servo Drive.
Timing Chart for Saving
Servo Parameters
SAVE SERVO PARAMETER can be executed while the corresponding axis is
operating (Busy Flag ON).
When using Position Control Units with unit version 2.0 or later, any Servo
parameter save operations specified during an origin search will be performed
after the origin search has been completed.
SAVE SERVO PARAMETER, WRITE SERVO PARAMETER, and READ
SERVO PARAMETER cannot be executed on one axis at the same time.
• Saving Servo Parameters during Origin Searches for Position Control
Units with Unit Version 2.0 or Later
When execution of SAVE SERVO PARAMETER has completed, the Servo
Parameter Transferring Flag (word b, bit 14) turns OFF.
050A hex
0002 hex
2881 hex
14
Pn50A
2881
14
MECHATROLINK
CPU Unit
PCU
Servo Drive
Axis Operating Output
Memory Area
Word a+1
Word b
Word a+20
Word a+19
Word a+18
Word a+17
---
Axis Operating Input
Memory Area
SAVE SERVO PARAMETER Bit
Servo Parameter No. (Pn50A)
Parameter size (2 bytes)
Set value (2881)
Servo Parameters Transferring Flag (ON while transferring)
a = Beginning word of Axis Operating Output Areas specified in Common Para (Axis No.
−
1)
×
25
b = Beginning word of Axis Operating Input Areas specified in Common Para (Axis No.
−
1)
×
25
Internal memory and
non-volatile memory
2
00002881 hex
050A hex
Servo Parameter No. (word a+17)
Parameter size (word a+18)
Write data (words a+19, a+20)
SAVE SERVO PARAMETER Bit
(word a+1, bit 14)
Servo Parameter Transferring Flag
(word b, bit 14)
Busy Flag (word b, bit 13)
For a parameter size of two bytes, only the
rightmost word (word a+19) of the write data is
used, and the data in the leftmost word (word
a+20) is ignored.
The Servo Parameter Transferring Flag turns
ON for at least one cycle time when the
command to transfer the parameter is received.
The status of the Busy Flag does not change
when Servo Parameters are being written.
When using Position Control Units with unit version
2.0 or later, any Servo parameter save operations
specified during an origin search will be performed
after the origin search has been completed.
Origin search operation in progress
Origin search operation completed
SAVE SERVO PARAMETER Bit
(word a+1, bit 14)
Servo Parameter Transferring Flag
(word b, bit 14)
Busy Flag (word b, bit 13)
Содержание CJ1W-MA - REV 10-2008
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 21: ...xxii ...
Страница 57: ...30 Starting Operation Section 2 2 ...
Страница 97: ...70 Wiring Section 3 4 ...
Страница 247: ...220 Transferring Servo Parameters Section 5 3 ...
Страница 281: ...254 Standard Settings for Servo Drives Using MECHATROLINK Section 6 4 ...
Страница 343: ...316 Absolute Encoder Origin Section 8 6 ...
Страница 375: ...348 Linear Interpolation Section 9 7 ...
Страница 423: ...396 DEVIATION COUNTER RESET Section 10 10 ...
Страница 631: ...604 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Страница 641: ...614 Index ...
Страница 643: ...616 Revision History ...