93
Common Parameter Area
Section 4-3
4-3-2
Common Parameter Details
The data set in the Common Parameter Area is as follows:
Data Details
Axis Operating Output Memory Area Designation
Specifies the words allocated for the Axis Operating Output Memory Areas.
0000 hex:
No setting (default setting)
00B0 hex:
CIO Area
00B1 hex:
Work Area
00B2 hex:
Holding Area
00B3 hex:
Auxiliary Area
0082 hex:
DM Area
0050 to 0059, 005A, 005B, 005C hex:
EM Area (005
@
hex:
@
= EM Bank No.)
Beginning Word of Axis Operating Output Memory Areas
Specifies the beginning word of the Axis Operating Output Memory Areas.
The Axis Operating Output Memory Area designation and the word deter-
mined using this parameter are used as the beginning word of the Operat-
ing Output Memory Area for Axis 1. Each axis is allocated 25 words in
sequence up to the highest axis number registered in the scan list.
1857 hex
00 (fixed)
07 to 04
03 to 00
C2 master connection:
0: No C2 master (default setting)
1: C2 master connected
Number of communications retries:
Set value: 0 to 7, F
The default setting 0 is the same as when the number of
retries is set to 1.
C2 mas-
ter con-
nection
Number
of com-
munica-
tions
retries
PCU's
address
Contents
Setting
Bits 08 to 15
Bits 00 to 07
Unit address
Name
Enable timing
1838 hex
Axis Operating Output Memory Area designa-
tion
At powerup or
restart.
1839 hex
Beginning word of Axis Operating Output Mem-
ory Areas
183A hex
Axis Operating Input Memory Area designation
183B hex
Beginning word of Axis Operating Input Memory
Areas
Data con-
figuration
15
08 07
00
Data setting range
Default
1838 hex
00B0 to 00B3, 0082,
0050 to 005C hex
0000
1839 hex
0000 to 7FFF hex
0000
183A hex
00B0 to 00B3, 0082,
0050 to 005C hex
0000
183B hex
0000 to 7FFF hex
0000
Axis Operating Output Memory Area designation
Beginning word of Axis Operating Output Memory
Areas
Axis Operating Input Memory Area designation
Beginning word of Axis Operating Input Memory
Areas
Содержание CJ1W-MA - REV 10-2008
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 21: ...xxii ...
Страница 57: ...30 Starting Operation Section 2 2 ...
Страница 97: ...70 Wiring Section 3 4 ...
Страница 247: ...220 Transferring Servo Parameters Section 5 3 ...
Страница 281: ...254 Standard Settings for Servo Drives Using MECHATROLINK Section 6 4 ...
Страница 343: ...316 Absolute Encoder Origin Section 8 6 ...
Страница 375: ...348 Linear Interpolation Section 9 7 ...
Страница 423: ...396 DEVIATION COUNTER RESET Section 10 10 ...
Страница 631: ...604 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Страница 641: ...614 Index ...