242
MECHATROLINK Communications Control
Section 6-3
Note
If an axis warning occurs (Warning Flag = 1), the PCU’s command response
time is delayed due to the PCU’s warning processing. The PCU processing
time required after receiving a command from the CPU Unit until the com-
mand is sent using MECHATROLINK communications is one MECHA-
TROLINK communications cycle if an axis warning has not occurred, and
three MECHATROLINK communications cycles if an axis warning has
occurred. If the machine’s operation would be affected by the PCU’s com-
mand response time, clear the axis warning status using ERROR RESET or
set the Servo Drive settings so that the warnings will not occur. For details on
the PCU’s command response time, refer to
Command Response Time
in
Appendix A Performance Characteristics
.
6-3-4
Rejoining the Connection
Overview
The rejoin function can be used to rejoin the connection for an axis for which
operations are not possible using MECHATROLINK communications either
when initially establishing the connection or after the connection has been
established.
This function can be used only with Position Control Units with unit version 2.0
or later.
If any axis registered in the scan list is in either of the following conditions, the
error cannot be cleared with the normal error reset procedure and axis opera-
tions will not be possible from the Position Control Unit.
• If an axis cannot be detected and MECHATROLINK communications cannot
be started within 10 s after executing the connection command (An MLK ini-
tialization error (Unit error code: 0020 (hex)) will occur.)
• If a synchronous communications alarm (axis error code: 3010 (hex)) occurs
or a communications alarm (axis error: 3011 (hex)) occurs
To restart communications for the axis for which axis operations are not possi-
ble with Position Control Units with unit version 1.3 or earlier, the connection
must be broken and MECHATROLINK communications must be stopped for
all axes, and then connection must be re-established.
Содержание CJ1W-MA - REV 10-2008
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 21: ...xxii ...
Страница 57: ...30 Starting Operation Section 2 2 ...
Страница 97: ...70 Wiring Section 3 4 ...
Страница 247: ...220 Transferring Servo Parameters Section 5 3 ...
Страница 281: ...254 Standard Settings for Servo Drives Using MECHATROLINK Section 6 4 ...
Страница 343: ...316 Absolute Encoder Origin Section 8 6 ...
Страница 375: ...348 Linear Interpolation Section 9 7 ...
Страница 423: ...396 DEVIATION COUNTER RESET Section 10 10 ...
Страница 631: ...604 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Страница 641: ...614 Index ...
Страница 643: ...616 Revision History ...