![Omron CJ1W-MA - REV 10-2008 Скачать руководство пользователя страница 308](http://html1.mh-extra.com/html/omron/cj1w-ma-rev-10-2008/cj1w-ma-rev-10-2008_operation-manual_742343308.webp)
281
Origin Search Operation
Section 8-2
When using an absolute encoder, make sure that the settings for the encoder
type in the Axis Parameters and
Operation Switch when Using Absolute
Encoder
(Pn00B for G Series and Pn002.2 for W Series) in the Servo Param-
eters match.
A motor with an absolute encoder cannot be used with a SMARTSTEP Junior
Servo Drive. When using a SMARTSTEP Junior Servo Drive, Pn002.2 is not
supported. Use the Servo Drive as for an incremental encoder.
If the settings do not agree, origin searches may not be possible and other
malfunctions may occur.
Command Unit Parameters
The command unit default setting is pulses.
G-series Acceleration/Deceleration Constants
Model
Parameter
No.
Parameter name
Unit
Setting
range
Parameter
size
Default
setting
R88D-GN
@
-
ML2
Pn205
Electronic gear ratio 1 (numerator)
---
1 to
1073741824
4
1
Pn206
Electronic gear ratio 2 (denominator)
---
1 to
1073741824
4
1
R88D-WT
@
Pn202
Electronic gear ratio G1 (numerator)
---
1 to 65535
2
4
Pn203
Electronic gear ratio G2 (denominator)
---
1 to 65535
2
1
R88D-WN
@
-
ML2
Pn20E
Electronic gear ratio G1 (numerator)
---
1 to
1073741824
4
4
Pn210
Electronic gear ratio G2 (denominator)
---
1 to
1073741824
4
1
SMART-
STEP Junior
Pn20E
Electronic gear ratio G1 (numerator)
---
1 to
1073741824
4
1
Pn210
Electronic gear ratio G2 (denominator)
---
1 to
1073741824
4
1
Type
Parame-
ter No.
Parameter name
Unit
Setting
range
Parame-
ter size
Default
setting
Accelera-
tion/
decelera-
tion con-
stants
Pn107
Linear acceleration con-
stant
10,000
command
units/s
2
−
32768
to 32767
2
100
Pn10A
Linear deceleration con-
stant
10,000
command
units/s
2
−
32768
to 32767
2
100
Accelera-
tion/
decelera-
tion filters
Pn10E
Moving average time
0.1 ms
0 to 5100 2
0
Содержание CJ1W-MA - REV 10-2008
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 21: ...xxii ...
Страница 57: ...30 Starting Operation Section 2 2 ...
Страница 97: ...70 Wiring Section 3 4 ...
Страница 247: ...220 Transferring Servo Parameters Section 5 3 ...
Страница 281: ...254 Standard Settings for Servo Drives Using MECHATROLINK Section 6 4 ...
Страница 343: ...316 Absolute Encoder Origin Section 8 6 ...
Страница 375: ...348 Linear Interpolation Section 9 7 ...
Страница 423: ...396 DEVIATION COUNTER RESET Section 10 10 ...
Страница 631: ...604 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Страница 641: ...614 Index ...
Страница 643: ...616 Revision History ...