234
MECHATROLINK Communications Control
Section 6-3
The operation of the Axis Communications Status Flag depends on the unit
version of the PCU as shown in the following table
With unit version 1.3 or earlier, once MECHATROLINK communications have
been started by establishing connections, the Axis Communications Status
Flags will not change unless communications are disconnected (including
Unit errors that required disconnection).
With unit version 2.0 or later, the Axis Communications Status Flags will turn
OFF after connections have been established whenever axis operation
becomes impossible due to a communications error (synchronous communi-
cations alarm or communications alarm).
Refer to
6-3-3 MECHATROLINK Communications Errors
for information on
errors that occur when establishing connections.
The Axis Communications Status Flags are allocated in CIO 1522 + (unit
number
×
25).
Unit version
Setting conditions
Resetting conditions
Unit version 1.3 or
earlier
• The flags will turn ON when
connections are made for
the axes registered in the
scan list and MECHA-
TROLINK communications
start.
• The flags will remain OFF
when MECHATROLINK
communications cannot be
started when connections
are made for the axes regis-
tered in the scan list.
• The flags will turn OFF if
MECHATROLINK communi-
cations stop because the
axis is disconnected.
• The flags will turn OFF if a
Unit error occurs that
requires disconnection.
Unit version 2.0 or
later
• The flags will turn ON when
connections are made for
the axes registered in the
scan list and MECHA-
TROLINK communications
start.
• The flags will turn ON when
the rejoin function is used to
start MECHATROLINK com-
munications for an axis reg-
istered in the scan list.
• The flags will remain OFF
when MECHATROLINK
communications cannot be
started when connections
are made for the axes regis-
tered in the scan list.
• The flags will turn OFF if
MECHATROLINK communi-
cations stop because the
axis is disconnected.
• The flags will turn OFF if a
Unit error occurs that
requires disconnection.
• The flags will turn OFF
whenever a communica-
tions error occurs after
MECHATROLINK communi-
cations have been started for
the axis.
Содержание CJ1W-MA - REV 10-2008
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 21: ...xxii ...
Страница 57: ...30 Starting Operation Section 2 2 ...
Страница 97: ...70 Wiring Section 3 4 ...
Страница 247: ...220 Transferring Servo Parameters Section 5 3 ...
Страница 281: ...254 Standard Settings for Servo Drives Using MECHATROLINK Section 6 4 ...
Страница 343: ...316 Absolute Encoder Origin Section 8 6 ...
Страница 375: ...348 Linear Interpolation Section 9 7 ...
Страница 423: ...396 DEVIATION COUNTER RESET Section 10 10 ...
Страница 631: ...604 Additional Functions for the CJ1W NCF71 MA Appendix F ...
Страница 641: ...614 Index ...
Страница 643: ...616 Revision History ...