Installation and Operation Guide
ED-DT318B
Drive Train Systems with Traction Control, Inverter/Controller, and Motor with 2 Speed Transmission
BC353060341319en-000101
Revision D
© Danfoss | November 2020 | 95
Classified as Business
16
15
14
13
12
11
10
9
MCU Motor Speed msB
8
7
6
5
4
3
2
1
MCU Motor Speed lsB
7.3.3.1
MCU Inverter Fault
dbc ref:
TCUStat3_MCUInverterFault
lsb:
64
msb:
64
Offset:
0
Scale Factor: 1
Min Value:
0
Max Value:
1
Units:
Boolean
Description: True
An MCU Inverter Fault is occurring.
False
No MCU Inverter Fault is occurring.
MCU inverter faults are power switch protection events. Too much heat or too much current can
damage the switches, so the MCU protects them and sets this bit while it is doing so. Too much
heat normally means that coolant loss has occurred, and the controller turns off the switches in
response. Too much current causes the controller to limit its torque by half.
7.3.3.2
MCU Inverter Fault History
dbc ref:
TCUStat3_MCUInverterFaultHistory
lsb:
63
msb:
63
Offset:
0
Scale Factor: 1
Min Value:
0
Max Value:
1
Units:
Boolean
Description: True
MCU
Inverter Fault
has been set to True at some point since the last time MCU power
was cycled.
False
MCU
Inverter Fault
has not been set to True at any point since the last time MCU power
was cycled.