
Installation and Operation Guide
ED-DT318B
Drive Train Systems with Traction Control, Inverter/Controller, and Motor with 2 Speed Transmission
BC353060341319en-000101
Revision D
© Danfoss | November 2020 | 51
Classified as Business
Cause
Maximum Motoring
Limits
Maximum
Regeneration Limits
Bus Voltage under Customer Battery Min
3%
NA
Stall conditions
10%
10%
Bus current over Positive Current
26%
NA
Bus current under Negative Current
NA
24%
Disconnected Temperature Sensor
50%
50%
Inverter Fault
50%
50%
Bad switch safety
50%
50%
Incorrect position offset
50%
50%
Over Positive Phase Advance limit
50%
50%
Under Negative Phase Advance limit
50%
50%
Variable Back EMF saturated high
50%
50%
Variable Back EMF saturated low
50%
50%
Bad controller calibration
51%
51%
Motor Leg current Over Current
51%
51%
Invalid Sensor voltage
52%
52%
Apparent Rotor Movement
52%
52%
Error with leg current sensors
53%
53%
Current Transducer Fault
53%
53%
1.
If the “Allow Braking” box in the System Configuration is checked, the system will be able to apply
regeneration torque to slow down the motor. Otherwise, the limit will be 0%.
When more than one limiting factor is present, the lowest limitation dominates. The most serious motoring
limitation is Over Speed. If configured to do so, this limitation can actually cause motor regeneration in order to
slow down the speed. The most serious regeneration limitation is Over Safety Voltage. This limitation can
actually change the motor’s control mode while the condition exists because the inverter will be destroyed if the
voltage remains above the allowable value. This control mode, called Forced Voltage Control, takes priority over
any other limit.
Содержание ED-DT318B
Страница 185: ......