VAR4 / VAR12 / VAR20 - Operation Manual
Is
Page 299 of 308
3
sue: 03 complete, approved
23.1.3 Default
Settings
Table 2
VAR Router Default Settings
Setting Default
Value
VAR Route
VAR Router access code
‘1999’ User 1
‘0999’ User 2
VAR Router ID
01
VAR Router name
Blank
Date / Time
Current date / time
Report over-temperature
No
Maximum temperature
70°C
RS232 port modes
CTS disabled / Direct Connect
Fault sounder during emergency
Enabled
Remote fault output 1
Active Sounder
Remote fault output 2 Active
Indicator
Host Protocol
Host protocol routing timeout
Enabled / 1min
Host protocol fault timeout
Disabled / 60s
Host protocol ‘make route’ message
Chime supported
Password control
Menu and Host / No warning message
Operation Mode
Stand-alone
Number of Network Channels = 0
Input
Input Type (Mic/Line)
Unused
Inputs 1 an 2 = Fire Microphone
Input Gain
−
14dB (microphones)
−
20dB (DVAs)
−
25dB (music A and B)
Input name
MIC/LINE nn
nn=input number
Input ANS
Enabled / Not ANS Tolerant
Class
High Emergency (fire mic. and LDVA #1)
Low Emergency (LDVA #2)
Non Emergency (other audio sources)
Priority
Fire microphone on input 1: 1
Fire microphone on input 2: 2
Other microphones: 7
LDVA: 3
SDVA: 5
Background music: 19
Output gain (relative gain)
0dB
EQ
0dB all bands / HPF=On
Fade 00
Input sensitivity
Line
Input surveillance
On
Input surveillance sensitivity
−
40dB
Input Phantom power
Off
Chime type
Off
Chime level
−
12dB
Содержание VAR12