VAR4 / VAR12 / VAR20 - Operation Manual
sue: 03 complete, approved
Is
Page 64 of 308
6.3.4.2.3 Configuring
an
Amplifier’s AC Surveillance Interval
As standard the VAR Router output is configured to generate a pulsed surveillance tone, as described in
Section “
12.4 Surveillance Tone Generation Configuration
”.
The maximum interval between surveillance tone pulses for pulsed surveillance tones can be configured.
Once set, the system must see pulses at this interval or more regularly. If pulses are not received within this
interval a fault will be reported.
Tone
Tone
Interval
In order to set the AC surveillance interval proceed as follows.
1. Select
Configuration
Æ
Frames
.
2. Scroll and select a mainframe from the configured mainframe list:
[Frame#nn - ]
Default values: n.a.
Note:
If no mainframe is configured, then a warning message will be displayed.
The mainframe description will be shown on the right side of the display, if defined.
3. Move to, scroll, and select a slot from the slot list:
Commission Description Temp [Slot#n]
Default values: ‘Slot#1’
Possible slots: 1 to 4
Note:
If the selected slot is not configured, then a warning message will be displayed.
4. Move to, and select the
AC Level
menu item:
Description [AC Level] DC Line Earth
5. Move to, and select the
Interval
menu item:
Frequency Thresholds [Interval]
6. Scroll the interval until the required value is displayed:
[Interval(s)=00]
Default values: ‘00’
Possible values: 00 to 50 seconds
Note:
The standard value for an ASL Amplifier Mainframe is 20 seconds.
7. Commission the amplifier by pressing the SELECT key, or cancel by pressing the BACK key.
The system will return to the parent menu after 3 seconds on pressing the SELECT key, or immediately
on pressing the BACK key.