658
Auxiliary Area Allocations by Function
Appendix C
Communications
Networks
Network Communications Information
Information When Automatically Allocating Communications Ports
Name
Address
Description
Access
Updated
Communications Port
Enabled Flags
A202.00 to
A202.07
ON when a network instruction or background execution
can be executed with the corresponding port number.
Bits 00 to 07 correspond to communications ports 0 to 7.
Read-only
Communications Port Com-
pletion Codes
A203 to
A210
These words contain the completion codes for the corre-
sponding port numbers when network instructions have
been executed. The corresponding word will be cleared
when background execution has been completed.
Words A203 to A210 correspond to communications
ports 0 to 7.
Read-only
Communications Port Error
Flags
A219.00 to
A219.07
ON when an error occurred during execution of a net-
work instruction.
OFF when a normal response is returned.
Bits 00 to 07 correspond to communications ports 0 to 7.
Read-only
Name
Address
Description
Access
Updated
Network Communications
Port Allocation Enabled Flag
A202.15
ON when there is a communications port available for
automatic allocation.
Note
Use this flag to confirm whether a communica-
tions port is available for automatic allocation
before executing communications instructions
when using 9 or more communications instruc-
tions simultaneously.
Read-only
First Cycle Flags after Net-
work Communications Fin-
ished
A214.00 to
A214.07
Each flag will turn ON for just one cycle after communi-
cations have been completed. Bits 00 to 07 correspond
to ports 0 to 7. Use the Used Communications Port Num-
ber stored in A218 to determine which flag to access.
Note
These flags are not effective until the next cycle
after the communications instruction is executed.
Delay accessing them for at least one cycle.
Read-only
First Cycle Flags after Net-
work Communications Error
A215.00 to
A215.07
Each flag will turn ON for just one cycle after a communi-
cations error occurs. Bits 00 to 07 correspond to ports 0
to 7. Use the Used Communications Port Number stored
in A218 to determine which flag to access. Determine the
cause of the error according to the Communications Port
Completion Codes stored in A203 to A210.
Note
These flags are not effective until the next cycle
after the communications instruction is executed.
Delay accessing them for at least one cycle.
Read-only
Network Communications
Completion Code Storage
Address
A216 to
A217
The completion code for a communications instruction is
automatically stored at the address with the I/O memory
address given in these words.
Place this address into an index register and use indirect
addressing through the index register to read the com-
munications completion code.
Read-only
Used Communications Port
Numbers
A218
Stores the communications port numbers used when a
communications instruction is executed using automatic
communication port allocations.
0000 to 0007 hex: Communications port 0 to 7
Read-only
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......