260
Pulse Outputs
Section 5-3
Explanation of the Origin Search Parameters
Operating Mode
The operating mode parameter specifies the kind of I/O signals that are used
in the origin search. The 3 operating modes indicate whether the Error
Counter Reset Output and Positioning Completed Input are used.
The following table shows the proper operating mode settings for different
drivers and applications.
Note
There are stepping motor drivers that are equipped with a positioning com-
pleted signal like a Servo driver. Operating modes 1 and 2 can be used with
these stepping motor drivers.
■
Remarks: Operations Detecting the Origin During Deceleration from High
Speed
Operating Mode 0 (without Error Counter Reset Output, without
Positioning Completed Input)
Connect the sensor's open collector output signal to the Origin Input Signal.
The Origin Input Signal's response time is 0.1 ms when set as a NO contact.
When the Origin Proximity Input Signal is received, the motor will begin decel-
erating from the origin search high speed to the origin search proximity speed.
In this operating mode, the Origin Input Signal will be detected if it is received
during this deceleration and an Origin Input Signal Error (error code 0202) will
be generated. In this case, the motor will decelerate to a stop.
Operating
mode
I/O signal
Remarks
Origin Input
Signal
Error Counter
Reset Output
Positioning Completed
Input
Operation when the origin is
detected during deceleration from
the origin search's high speed
0
The origin position
is determined
when the Origin
Input Signal goes
from OFF to ON.
Not used.
The origin search
operation ends
after the origin is
detected.
Not used.
The Origin Input Signal will be
detected during deceleration. An Ori-
gin Input Signal Error (error code
0202) will occur and the motor will
decelerate to a stop.
1
Goes ON for 20 to
30 ms when the
origin is detected.
The Origin Input Signal will not be
detected during deceleration. When
the Origin Input Signal is detected
after the motor has reached the prox-
imity speed for origin search, the
motor will be stopped and the origin
search operation will end.
2
After the origin is
detected, the origin
search will not be end
until the Positioning
Completed Input is
received from the driver.
Driver
Remarks
Operating mode
Stepping motor driver (See note.)
0
Servo driver
Use this mode when you want to
reduce the processing time, even at the
expense of positioning accuracy. (The
Servo Driver's positioning complete
signal is not used.)
1
Use this mode when you want high
positioning accuracy. (The Servo
Driver's positioning complete signal is
used.)
2
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......