![background image](http://html1.mh-extra.com/html/omron/sysmac-cp1h/sysmac-cp1h_operation-manual_741321638.webp)
604
Error Classification and Confirmation
Section 11-1
Non-fatal Errors
Auxiliary Area
■
Error Code Storage Word
The error code is stored in A400 when an error occurs. If two or more errors
occur at the same time, the most serious error will be stored.
■
Error Flags
Flags that indicate the type of error are allocated in the Auxiliary Area.
■
Error Information
This area indicates specific information on the meaning of error flags and pro-
vides information on error location and error details.
4.1.
→
0.1.
→
FAL instruction executed for FAL number 001
:
:
4.2.
→
0.0.
→
FAL instruction executed for FAL number 256
:
:
4.2.
→
f.f.
→
FAL instruction executed for FAL number 511
0.0.
→
f.1.
→
Flash memory error
0.0.
→
8.b.
→
→
→
Unit number of interrupt task error occurrence
Interrupt task error
Example Displays of Unit Numbers for which an Interrupt Task Error Has Occurred
→
8.0.
→
→
0.0.
Special I/O Unit with unit number 1
→
8.0.
→
→
0.f.
Special I/O Unit with unit number 15
→
8.0.
→
→
s.f.
Special I/O Unit with unit number 95
0.0.
→
9.b.
→
→
→
Location of PLC Setup error
PLC Setup error
Example Displays for Locations of PLC Setup Errors
→
0.0.
→
→
0.0.
PLC Setup internal address: 0000 hex
→
0.1.
→
→
f.f.
PLC Setup internal address: 01FF hex
0.0.
→
8.a.
→
Built-in analog I/O error
0.2.
→
0.0.
→
CPU bus error for CPU Bus Unit with unit number 0
:
:
0.2.
→
0.f.
→
CPU bus error for CPU Bus Unit with unit number F
0.3.
→
0.0.
→
Error for Special I/O Unit with unit number 0
:
:
0.3.
→
s.f.
→
Error for Special I/O Unit with unit number 95
0.3.
→
f.f.
→
Error for Special I/O Unit with unknown unit number
0.0.
→
d.1.
→
Option Board error for option slot 1
0.0.
→
d.2.
→
Option Board error for option slot 2
0.0.
→
f.7.
→
Battery error
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......