219
High-speed Counters
Section 5-2
X/XA CPU Units
Input Terminal Arrangement
Input Function Settings in the PLC Setup
The CPU Unit’s built-in inputs can be set for high-speed counter inputs in the
PLC Setup’s Built-in Input Tab. (When an input is set for use as a high-speed
counter input, the corresponding words and bits cannot be used for general-
purpose (normal) inputs, input interrupts, or quick-response inputs.)
00
02
04
06
08
10
00
02
04
06
08
10
L1
L2/N COM
01
03
05
07
09
11
01
03
05
07
09
11
LG
Inputs (CIO 0)
Inputs (CIO 1)
High-speed counter 1
(Phase B, Decrement, or
Direction input)
Upper Terminal Block
(Example: AC Power
Supply Modules)
High-speed counter 1
(Phase Z or Reset input)
High-speed counter 1
(Phase A, Increment, or
Count input)
High-speed counter 3
(Phase B, Decrement,
or Direction input)
High-speed counter 3
(Phase Z or Reset input)
High-speed counter 3
(Phase A, Increment, or
Count input)
High-speed counter 0
(Phase A, Increment,
or Count input)
High-speed counter 2
(Phase A, Increment, or
Count input)
High-speed counter 2
(Phase Z or Reset input)
High-speed counter 2
(Phase B, Decrement, or
Direction input)
High-speed counter 0
(Phase B, Decrement, or
Direction input)
High-speed counter 0
(Phase Z or Reset input)
Input terminal
block
Bit function when the high-speed counter is enabled by
selecting “Use high-speed counter
” in the PLC Setup
Word
Bit
CIO 0
00
---
01
High-speed counter 2 (Phase Z or Reset input)
02
High-speed counter 1 (Phase Z or Reset input)
03
High-speed counter 0 (Phase Z or Reset input)
04
High-speed counter 2 (Phase A, Increment, or Count input)
05
High-speed counter 2 (Phase B, Decrement, or Direction input)
06
High-speed counter 1 (Phase A, Increment, or Count input)
07
High-speed counter 1 (Phase B, Decrement, or Direction input)
08
High-speed counter 0 (Phase A, Increment, or Count input)
09
High-speed counter 0 (Phase B, Decrement, or Direction input)
10
High-speed counter 3 (Phase A, Increment, or Count input)
11
High-speed counter 3 (Phase B, Decrement, or Direction input)
CIO 1
00
High-speed counter 3 (Phase Z or Reset input)
01 to 11
---
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......