374
Memory Cassette Functions
Section 6-5
Reading Data from
the Memory Cassette
to the CPU Unit
The CX-Programmer's Memory Cassette function can be used to read data
stored on the Memory Cassette, and transfer it to the corresponding areas in
the CPU Unit. The data to be read can be individually specified.
This function can be used for operations such as writing the required backup
data to the CPU Unit for maintenance.
Precautions when
Using the Memory
Cassette Data
Transfer Function
• In order for Memory Cassette data to be transferred, the Memory Cas-
sette must be mounted in the CPU Unit.
• The BKUP indicator lights while a Memory Cassette data transfer or verifi-
cation is in progress. At the same time, the remaining amount of data to
be transferred or verified is displayed as a percentage in the 7-segment
LED. (When the transfer or is completed,
00
flashes for 5 seconds and
then the display is cleared. If the data transfer fails, er flashes for 5 sec-
onds and then the display is cleared.
While the BKUP and 7-segment LED indicators are flashing, 1) do not turn
OFF the power supply to the PLC and 2) do not remove the Memory Cas-
sette. If either of these is done, in the worst case it may make the Memory
Cassette unusable.
• Memory Cassette data transfers and verification are possible only when
the CPU Unit operating mode is PROGRAM mode. The Memory Cassette
transfer function cannot be used in either RUN or MONITOR mode.
• The operating mode cannot be switched from PROGRAM mode to RUN
or MONITOR mode while a Memory Cassette data transfer or verification
is in progress.
Programs, parameters, DM initial
values, comment memory, etc.
(Can be specified individually.)
CP1H CPU Unit
Data in CPU
Unit
Reading
CX-Programmer
Reading from Memory
Cassette to CPU Unit
CP1W-ME05M
Memory Cassette
99
98
97
03
02
01
00
er.
Flashes (for 5 s)
7-segment LED display
Countdown
Flashes (for 5 s)
When a transmission
error occurs
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......