397
Analog Input Units
Section 7-2
Averaging Function
For analog inputs, the averaging function operates when the averaging bit is
set to 1. The averaging function outputs the average (a moving average) of
the last eight input values as the converted value. If there is only a slight vari-
ation in inputs, it is handled by the averaging function as a smooth input.
The averaging function stores the average (a moving average) of the last eight
input values as the converted value. Use this function to smooth inputs that
vary at a short interval.
Open-circuit Detection
Function
The open-circuit detection function is activated when the input range is set to
1 to 5 V and the voltage drops below 0.8 V, or when the input range is set to 4
to 20 mA and the current drops below 3.2 mA. When the open-circuit detec-
tion function is activated, the converted data will be set to 8,000.
The time for enabling or clearing the open-circuit detection function is the
same as the time for converting the data. If the input returns to the convertible
range, the open-circuit detection is cleared automatically and the output
returns to the normal range.
Procedure
Writing Set Data and
Reading A/D Converted
Values
4 mA
20 mA
20.8 mA
3.2 mA
FDA8 (
−
600)
3138 (12600)
2EE0 (12000)
0000 (0)
0 mA
Converted Data
Hexadecimal (Decimal)
Connect and wire Units.
Create a ladder program.
• Connect Analog Input Units.
• Wire to analog output devices.
• Write set data to output words (n+1, n+2).
• Set use of inputs.
• Select input signals using range codes.
• Set use of averaging.
• Read A/D converted values from input words
(m+1 to m+4).
• For current inputs, confirm that there is no open
circuit.
CPU Unit
MOV(021)
Set data (inputs 1, 2)
Set data (inputs 3, 4)
Analog input 3 converted value
Analog input 4 converted value
Analog Input Unit
Ladder program
Analog input 1 converted value
Analog input 2 converted value
Analog devices
Temperature sensor
Pressure sensor
Speed sensor
Flow sensor
Voltage/current meter
Other devices
Writes the set data.
Reads the converted
value.
“m” is the last input word and “n” is
the last output word allocated to the
CPU Unit or previous Expansion
Unit or Expansion I/O Unit.
Word (n+1)
Word (n+2)
Word (m+1)
Word (m+2)
Word (m+3)
Word (m+4)
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......