482
CompoBus/S I/O Link Units
Section 7-6
(3) Unused bits in input word cannot be used as work bits.
Determining the Node
Number and Making DIP
Switch Settings
Node Number
• The CompoBus/S I/O Link Unit is a Slave Unit with 8 input bits and 8 out-
put bits. The node number setting is made using the DIP switch; the
inputs and outputs share the same node number.
• The range of possible node number settings is determined by the type of
PC the Master Unit is mounted to and the settings on the Master Unit. For
details refer to the
CompoBus/S Operation Manual
.
DIP Switch Settings
Use the DIP switch to set the CompoBus/S I/O Link Unit’s node number, com-
munications mode, and the status of output data when a communications
error occurs.
Note
Always turn OFF the power supply before changing the DIP switch settings.
Wiring the CompoBus/S
Communications Path
Wire the CompoBus/S communications path as shown in the following dia-
grams.
Pin labels
Contents
1
2
4
8
DR
HOLD
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1 = ON, 0 = OFF
ON
OFF
ON
OFF
Long-distance communications mode (See note.)
High-speed communications mode
Retain inputs after a communications error.
Clear inputs after a communications error.
ON
1
2
4
8
DR
HOLD
SW1
8 4 2 1
0 0 0 0
0 0 0 1
0 0 1 0
0 0 1 1
0 1 0 0
0 1 0 1
0 1 1 0
0 1 1 1
1 0 0 0
1 0 0 1
1 0 1 0
1 0 1 1
1 1 0 0
1 1 0 1
1 1 1 0
1 1 1 1
NODE NUMBER
SW1
Node Number
Setting
Note:
The long-distance communications
mode can be used only when one of
the following Master Units is
connected: C200HW-SRM21-V1,
CQM1-SRM21-V1, or SRM1-C0
@
-V2.
BD L
BD H
Connect the CompoBus/S Communications Cable.
BD L
BD H NC (BS+)
NC
NC (BS
−
)
These terminals are not used. They can
however be used as communications power
supply relay terminals.
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......