592
Program Transfer
Section 10-1
10-1 Program Transfer
The CX-Programmer is used to transfer the programs, PLC Setup, I/O mem-
ory data, and I/O comments to the CPU Unit with the CPU Unit in PROGRAM
mode. The following procedure is used.
1,2,3...
1.
Select
PLC - Transfer - To PLC.
The Download Options Dialog Box will be
displayed.
2.
Specify the items to transfer.
3.
Click the
OK
Button.
Note
The program data on a Memory Cassette can be automatic transferred when
the power is turned ON.
10-2 Trial Operation and Debugging
10-2-1 Forced Set/Reset
The CX-Programmer can force-set (ON) or reset (OFF) specified bits in the
CIO Area, Auxiliary Area, and HR Area, as well as timer/counter Completion
Flags. Forced status will take priority over status output from the program or
I/O refreshing. This status cannot be overwritten by instructions, and will be
stored regardless of the status of the program or external inputs until it is
cleared from the CX-Programmer.
Force-set/reset operations are used to force input and output during a trial
operation or to force certain conditions during debugging.
Force-set/reset operations can be executed in either MONITOR or PRO-
GRAM modes, but not in RUN mode.
Note
Turn ON the Forced Status Hold Bit (A500.13) and the IOM Hold Bit (A500.12)
at the same time to retain the status of bits that have been force-set or reset
when switching the operating mode.
Turn ON the Forced Status Hold Bit (A500.13) and the IOM Hold Bit
(A500.12), and set the Forced Status Hold Bit at Startup parameter in the PLC
Setup to retain the status of the Forced Status Hold Bit hold to retain the sta-
tus of bits that have been force-set or reset when turning OFF the power.
The following areas can be force-set and reset: CIO Area (I/O bits, data link
bits, CPU Bus Unit bits, Special I/O Unit bits, and work bits), Work Area, Timer
Completion Flags, HR Area, Counter Completion Flags.
CX-Programmer Operation
• Selecting bits for forced setting/resetting
• Selecting forced set or forced reset status
• Clearing forced status (also clearing all forced status at the same time)
Input ignored
CPU Unit
Forced ON regardless
of programming
Forced
set
Forced
set
Program
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......