612
Troubleshooting
Section 11-2
11-2-4 CPU Errors
■
CPU Unit Indicators
A CPU error or fatal error may have occurred if the ERR/ALM indicator lights
during operation (RUN mode or MONITOR mode), the RUN indicator turns
OFF, and operation stops. A CPU error may have occurred if nothing is shown
on the 7-segment display or the same message remains on the display.
CPU Errors
■
Reference Information
Note
Just as when a CPU error occurs, the RUN indicator will turn OFF and the
ERR/ALM indicator will light when a fatal error occurs. Connecting the CX-
Programmer, however, is possible for fatal errors but not for CPU errors. If the
CX-Programmer cannot be connected (online), a CPU error has probably
occurred.
11-2-5 Non-fatal Errors
A non-fatal error has occurred if both the RUN indicator and the ERR/ALM
indicator are lit during operation (i.e., in RUN or MONITOR mode).
■
CPU Unit Indicators
Information on the non-fatal error can be obtained from the error code on the
7-segment display and from the Error Tab Page of the CX-Programmer’s PLC
Error Window. Take corrective actions after checking error details using the
display messages and the Auxiliary Area Error Flags and error information.
• Errors are listed in the following table in order, with the most serious ones
first.
• If two or more errors occur at the same time, the most serious error code
will be stored in A400.
POWER
Lit
RUN
Not lit
ERR/ALM
Lit
INH
---
BKUP
---
PRPHL
---
POWER
RUN
INH
PRPHL
BKUP
ERR/ALM
Seven-segment
display
Probable cause and possible remedy
The display is not
lit or it is frozen.
A WDT (watchdog) error occurred in the CPU Unit. (This does
not occur in normal use.) Cycle the power supply. The Unit may
be faulty. Consult your OMRON representative.
Error flag
None
Error code (A400)
None
Error information
None
POWER
Lit
RUN
Lit
ERR/ALM
Flashing
INH
---
BKUP
---
PRPHL
---
POWER
RUN
INH
PRPHL
BKUP
ERR/ALM
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......