697
Auxiliary Area Allocations by Address
Appendix D
A532
All
Interrupt
Counter 0
Counter SV
Used for interrupt input 0 in counter
mode.
Sets the count value at which the
interrupt task will start. Interrupt task
140 will start when interrupt counter
0 has counted this number of pulses.
Retained when operation starts.
---
Retained
Retained
---
---
A533
All
Interrupt
Counter 1
Counter SV
Used for interrupt input 1 in counter
mode.
Sets the count value at which the
interrupt task will start. Interrupt task
141 will start when interrupt counter
1 has counted this number of pulses.
---
Retained
Retained
---
---
A534
All
Interrupt
Counter 2
Counter SV
Used for interrupt input 2 in counter
mode.
Sets the count value at which the
interrupt task will start. Interrupt task
142 will start when interrupt counter
2 has counted this number of pulses.
---
Retained
Retained
---
---
A535
All
Interrupt
Counter 3
Counter SV
Used for interrupt input 3 in counter
mode.
Sets the count value at which the
interrupt task will start. Interrupt task
143 will start when interrupt counter
3 has counted this number of pulses.
---
Retained
Retained
---
---
A536
All
Interrupt
Counter 0
Counter PV
These words contain the interrupt
counter PVs for interrupt inputs oper-
ating in counter mode.
In increment mode, the counter PV
starts incrementing from 0. When the
counter PV reaches the counter SV,
the PV is automatically reset to 0.
In decrement mode, the counter PV
starts decrementing from the counter
SV. When the counter PV reaches
the 0, the PV is automatically reset to
the SV.
Cleared when operation starts.
---
---
Retained
Refresh-
ed when
interrupt
is gener-
ated.
Refresh-
ed when
INI(880)
instruc-
tion is
executed.
---
A537
All
Interrupt
Counter 1
Counter PV
---
---
---
A538
All
Interrupt
Counter 2
Counter PV
---
---
---
A539
All
Interrupt
Counter 3
Counter PV
---
---
---
A540
A540.00 Pulse Out-
put 0 Reset
Bit
The pulse output 0 PV (contained in
A276 and A277) will be cleared when
this bit is turned ON.
---
---
Cleared
---
A276 and
A277
A540.08 Pulse Out-
put 0 CW
Limit Input
Signal Flag
This is the CW limit input signal for
pulse output 0, which is used in the
origin search. To use this signal,
write the input from the actual sensor
as an input condition in the ladder
program and output the result to this
flag.
---
---
Cleared
---
---
A540.09 Pulse Out-
put 0 CCW
Limit Input
Signal Flag
This is the CCW limit input signal for
pulse output 0, which is used in the
origin search. To use this signal,
write the input from the actual sensor
as an input condition in the ladder
program and output the result to this
flag.
---
---
Cleared
---
---
A540
A540.10 Pulse Out-
put 0 Posi-
tioning
Completed
Signal
This is the positioning completed
input signal used in the origin search
for pulse output 0. The input signal
from the servo driver is output to this
bit from the ladder program to enable
using the signal.
---
---
Cleared
---
Addresses
Name
Function
Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
Flags,
Settings
Word
Bits
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......