687
Auxiliary Area Allocations by Address
Appendix D
A402
A402.06 Special I/O
Unit Error Flag
(non-fatal
error)
ON when an error occurs in a data
exchange between the CPU Unit and
a Special I/O Unit (including an error
in the Special I/O Unit itself).
The CPU Unit will continue operating
and the ERR/ALM indicator on the
front of the CPU Unit will flash. The
Special I/O Unit where the error
occurred will stop operating and the
unit number of the Unit where the
data exchange error occurred is indi-
cated in A418 through A423.
(This flag will be turned OFF when
the error is cleared.)
ON: Error in
one or more
Units
OFF: No
errors in any
Unit
Cleared
Cleared
Refreshed
when error
occurs.
A418 to
A423
A402.07 CPU Bus Unit
Error Flag
(non-fatal
error)
ON when an error occurs in a data
exchange between the CPU Unit and
an CPU Bus Unit (including an error
in the CPU Bus Unit itself).
The CPU Unit will continue operating
and the ERR/ALM indicator on the
front of the CPU Unit will flash. The
CPU Bus Unit where the error
occurred will stop operating and the
unit number of the Unit where the
data exchange error occurred is indi-
cated in A417.
(This flag will be turned OFF when
the error is cleared.)
ON: Error in
one or more
Units
OFF: No error
in any Unit
Cleared
Cleared
Refreshed
when error
occurs.
A417
A402.10 PLC Setup
Error Flag
(non-fatal
error)
ON when there is a setting error in
the PLC Setup. The CPU Unit will
continue operating and the ERR/
ALM indicator on the front of the
CPU Unit will flash. The location of
the error will be written to A406.
(This flag will be turned OFF when
the error is cleared.)
ON: Error
OFF: No error
Cleared
Cleared
Refreshed
when error
occurs.
A406
A402.13 Interrupt Task
Error Flag
(non-fatal
error)
ON when the Detect Interrupt Task
Errors setting in the PLC Setup is set
to “Detect” and an interrupt task is
executed for more than 10 ms during
I/O refreshing of a Special I/O Unit.
This flag will also be turned ON if an
attempt is made to refresh a Special
I/O Unit’s I/O from an interrupt task
with IORF(097) while the Unit’s I/O is
being refreshed by cyclic I/O refresh-
ing (duplicate refreshing).
The CPU Unit will continue operating
and the ERR/ALM indicator on the
front of the CPU Unit will flash.
(This flag will be turned OFF when
the error is cleared.)
ON: Interrupt
task error
OFF: No error
Cleared
Cleared
Refreshed
when error
occurs.
A426,
PLC
Setup
(Detect
Interrupt
Task
Errors set-
ting)
A402.15 FAL Error Flag
(non-fatal
error)
ON when a non-fatal error is gener-
ated by executing FAL(006). The
CPU Unit will continue operating and
the ERR/ALM indicator on the front
of the CPU Unit will flash.
The bit in A360 to A391 that corre-
sponds to the FAL number specified
in FALS(006) will be turned ON and
the corresponding error code will be
written to A400. Error codes 4101 to
42FF correspond to FAL numbers
001 to 2FF (0 to 511).
(This flag will be turned OFF when
the error is cleared.)
ON:
FALS(006)
error occurred
OFF:
FALS(006)
not executed
Cleared
Cleared
Refreshed
when error
occurs.
A360 to
A391,
A400
Address
Name
Function
Settings
Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words
Bits
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......