694
Auxiliary Area Allocations by Address
Appendix D
A514
All
Number of
Power Inter-
ruptions
Contains the number of times that
power has been interrupted since the
power was first turned ON. The data
is stored in binary. To reset this
value, overwrite the current value
with 0000.
(This word is not cleared at startup,
but it is cleared when the Memory
Corruption Detected Flag (A395.11)
goes ON.)
0000 to FFFF
hexadecimal
Retained
Retained
Refresh-
ed when
power is
turned
ON.
A395.11
A515 to
A517
All
Operation
Start Time
The time that operation started as a
result of changing the operating
mode to RUN or MONITOR mode is
stored here in BCD.
A515.00 to A515.07: Seconds (00 to
59)
A515.08 to A515.15: Minutes (00 to
59)
A516.00 to A516.07: Hour (00 to 23)
A516.08 to A516.15: Day of month
(01 to 31)
A517.00 to A517.07: Month (01 to
12)
A517.08 to A517.15: Year (00 to 99)
Note
The previous start time is
stored after turning ON the
power supply until operation
is started.
See at left.
Retained
Retained
See at
left.
---
A518 to
A520
All
Operation
End Time
The time that operation stopped as a
result of changing the operating
mode to PROGRAM mode is stored
here in BCD.
A518.00 to A518.07: Seconds (00 to
59)
A518.08 to A518.15: Minutes (01 to
59)
A519.00 to A519.07: Hour (00 to 23)
A519.08 to A519.15: Day of month
(01 to 31)
A520.00 to A520.07: Month (01 to
12)
A520.08 to A520.15: Year (00 to 99)
Note
If an error occurs in operation,
the time of the error will be
stored. If the operating mode
is then changed to PRO-
GRAM mode, the time that
PROGRAM mode was
entered will be stored.
See at left.
Retained
Retained
See at
left.
---
A523
All
Total Power
ON Time
Contains the total time that the PLC
has been ON in 10-hour units. The
data is stored in binary and it is
updated every 10 hours. To reset this
value, overwrite the current value
with 0000.
(This word is not cleared at startup,
but it is cleared to 0000 when the
Memory Corruption Detected Flag
(A395.11) goes ON.)
0000 to FFFF
hexadecimal
Retained
Retained
---
---
Addresses
Name
Function
Settings
Status
after
mode
change
Status at
startup
Write
timing
Related
Flags,
Settings
Word
Bits
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......