611
Troubleshooting
Section 11-2
■
Reference Information
Cycle Time Too Long
■
Reference Information
Errors Created with FALS Instructions
■
Reference Information
Error flag
Program Error Flag, A401.09
Error code (A400)
80F0
Error information
Program error details, A294 to A299
Seven-segment
display
Probable cause and possible remedy
8.0.
→
9.f.
→
This error occurs when the cycle time PV exceeds the maximum
cycle time set in the PLC Setup. Review the program to decrease
the cycle time or change the maximum cycle time set in the PLC
Setup.
Refer to the Maximum Interrupt Task Processing Time (A440)
and study the maximum cycle time.
The cycle time can be decreased using the following methods.
• Separate instructions not being executed into different tasks.
• Consider using jump instructions for areas in the task that are
not executed.
• Prohibit cycle refreshing with Special I/O Units that do not
require exchange of cycle data.
Error flag
Cycle Time Too Long Error, A401.08
Error code (A400)
809F
Error information
---
Seven-segment display
Probable cause and possible remedy
c.1.
→
0.1.
→
FALS instruction
executed (FALS
number 001)
A FALS instruction was executed in the program to
create a fatal error.
C100 hex will be added to the FALS number (001 to
1FF hex) and the result will be stored in A400 as
error codes C101 to C2FF hex.
Check the conditions for executing FALS instruc-
tions and remove any causes for the user-defined
error.
c.2.
→
0.0.
→
FALS instruction
executed (FALS
number 256)
c.2.
→
f.f.
→
FALS instruction
executed (FALS
number 511)
Error flag
FALS Error Flag, A401.06
Error code (A400)
C101 to C2FF
Error information
---
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......