464
Temperature Sensor Units
Section 7-5
Open-circuit Detection
Function for Temperature
If the circuit is disconnected, the open-circuit detection function will operate
and the converted temperature data will be set to 7FFF.
Open-circuit Detection
Function for Analog
Inputs
The open-circuit detection function is activated when the input range is set to
1 to 5 V and the voltage drops below 0.8 V, or when the input range is set to 4
to 20 mA and the current drops below 3.2 mA. When the open-circuit detec-
tion function is activated, the converted data will be set to 8,000.
The time for enabling or clearing the open-circuit detection function is the
same as the time for converting the data. If the input returns to the convertible
range, the open-circuit detection is cleared automatically and the output
returns to the normal range.
Creating a Ladder
Program
Word Allocations
Temperature Sensor Units are allocated words in the same way as other CP-
series Expansion Units or Expansion I/O Units, in order of connection. A Tem-
perature Sensor Unit is allocated the next input words following the input
words of the CPU Unit or previous Expansion Unit or Expansion I/O Unit. Four
input words are allocated to CP1W-TS003.
Example
Converted Temperature Data
The converted temperature value will be stored in the input words allocated to
the Temperature Sensor Unit in 4-digit hexadecimal.
“m” is the last input word allocated to the CPU Unit, Expansion I/O Unit, or
Expansion Unit connected immediately before the Temperature Sensor Unit.
• Negative values are stored as 2’s complements.
• Data for range codes that include one digit after the decimal point are
stored without the decimal point, i.e., 10 times the actual value is stored.
• If the input temperature exceeds the maximum or minimum value in the
temperature input range that has been set by ±20
°
C or ±20
°
F, the dis-
played value will be held.
• If the circuit is disconnected, the open-circuit detection function will oper-
rate and the converted temperature data will be set to 7FFF.
• The open-circuit detection function will be automatically cleared and nor-
mal input temperature conversion will begin automatically when the input
temperature returns to the convertible range.
Input
Data conversion examples
Unit: 0.1
°
C
K or J
×
10
500.0
°
C
→
5000
→
1388 hex
−
20.0
°
C
→
−
200
→
FF38 hex
−
200.0
°
C
→
−
2000
→
F830 hex
None
CP1W-TS003
Temperature Sensor Unit
CP1H
Input word
addresses
Output word
addresses
CIO 0
CIO 1
CIO 100
CIO 101
CIO 2
CIO 3
CIO 4
CIO 5
m+1
Converted temperature data from input 0
m+2
Converted temperature data from input 1
m+3
Converted temperature data from input 2
m+4
Converted temperature data from input 3
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......