615
Troubleshooting
Section 11-2
Special I/O Unit Errors
■
Reference Information
Option Board Errors
■
Reference Information
Battery Error
■
Reference Information
Seven-segment display
Probable cause and possible remedy
0.3.
→
0.0.
→
Special I/O Unit
error, unit num-
ber 0
A data exchange error has occurred between the
CPU Unit and one of the Special I/O Units.
Note
Information on where the data exchange error
occurred (i.e., between the CPU Unit and what
Unit number) is stored in A418 to A423. Check
the Unit given in A418 to A423.
Refer to the manual for the relevant Unit and remove
the cause of the error. Then turn ON the Restart Bit
or cycle the power supply.
Replace the Unit if operation is not restored when the
Unit is restarted.
0.3.
→
s.f.
→
Special I/O Unit
error, unit num-
ber 95
0.3.
→
f.f.
→
Special I/O Unit
error, unit num-
ber unknown
Error flag
Special I/O Unit Error Flag, A402.06
Error code (A400)
0300 to 035F, 03FF
Error information
Special I/O Unit Error Unit Number Flags, A418 to A423
Seven-segment display
Probable cause and possible remedy
0.0.
→
d.1.
→
Option Board error
(option slot 1)
A315.13 will turn ON if the Option Board is
removed while the power is being supplied.
Turn OFF the power supply and then install the
Option Board again.
0.0.
→
d.2.
→
Option Board error
(option slot 2)
Error flags
Option Board Error Flag, A315.13
Other Non-fatal Error Flag, A402.00
Error code (A400)
---
Error information
---
Seven-segment
display
Probable cause and possible remedy
0.0.
→
f.7.
→
If the PLC Setup is set to detect battery errors, this error will occur
when there is an error in the battery in the CPU Unit (i.e., the volt-
age is low or a battery is not mounted). Check the battery connec-
tions.
When using battery-free operation, disable connecting battery
errors in the PLC Setup.
Error flag
Battery Error Flag, A402.04
Error code (A400)
00F7
Error information
---
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......