567
Memory Allocations
Section 9-9
9-9-2
DM Area Allocation
The memory allocation about system setup is shown as the following diagram.
These data will be allocated to the DM area of PLC. The beginning DM chan-
nel n is calculated by the following equation.
Note
1. DM area from n to n+154 can only display all of the settings stared in the
unit. Modification in this area is invalid to the CP1W-CIF41 Ethernet Option
Board.
2. DM area n+155 and n+156 will display the IP address used by the CP1W-
CIF41 when the power is turned ON.
3. When the IP address is illegal, such as using CLASS D, CLASS E IP
address, the values in words n+3 and n+155 will be different, and the
CP1W-CIF41 will temporarily use the default IP address (192.168.250.1).
Use this IP address to modify the IP address settings through Web
browser.
4. When the system settings are wrong, A525 can be used to reset CP1W-
CIF41.Refer to
Appendix C
and
Appendix D
for details.
n = D 300×(0xFD - Unit Address)
The following table describes the unit address for each option port.
Offset
D15 D0
n
Mode setting (2 bytes)
n+1
FINS/TCP port number (2 bytes)
n+2
FINS/UDP port number (2 bytes)
n+3
IP address (4 bytes)
n+5
Subnet mask (4 bytes)
n+7
Reserved (2 bytes)
n+8
IP address table (194 bytes)
n+105
IP router table (66 bytes)
n+138
FINS/TCP connection setup (22 bytes)
n+149
HTTP server setup (10 bytes)
n+154
FINS node address (2 bytes)
n+155
Using IP Address Display/Setting Area (4 bytes)
Option Port No.
I/O Capacity
Unit Address
Range of Status Area
Option port 1
14/20
0xFC
DM32300 to DM32456
30/40/60
0xFD
DM32000 to DM32156
Option port 2
30/40/60
0xFC
DM32300 to DM32456
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......