Connection Methods
Communications Modes and Ports
The following table shows the relationship between the communications ports and the communications modes
for the Serial Communications Option Boards.
Note
(1) The NT-AL001 Link Adapter can be used to convert between RS-232C and RS-422A/485 to enable
1:N communications.
(2) Use 4-wire connections between Link Adapters.
Models of Serial Communications Option Board
Note
The CP1W-CIF11 is a non-isolated board, so the maximum transmission distance is 50 m. For distances
over 50 m, use the RS-232C port on the CP1W-CIF01 and then connect through the NT-AL001 Link
Adapter, which is isolated. Doing so will enable a maximum transmission distance of 500 m.
Reducing Electrical Noise for External Wiring
Observe the following precautions when wiring communications cables, PLC power lines, and high-power
lines. When multi-conductor signal cable is being used, avoid using I/O wires and other control wires in the
same cable.
• If wiring racks are running in parallel, allow at least 300 mm between the racks.
Communications mode
RS-232C
CP1W-CIF01
RS-422A/485
CP1W-CIF11/CIF12
1:1
1:N
(See note 1.)
1:1 4-wire
1:N 4-wire
1:1 2-wire
1:N 2-wire
Host Link
YES
YES
(See note 2.)
YES
YES
No
No
Serial PLC Links
YES
YES
YES
YES
YES
YES
Serial Gateway
YES
YES
YES
YES
YES
YES
No-protocol
YES
YES
YES
YES
YES
YES
1:N NT Link
YES
YES
YES
YES
YES
YES
Model
Port
Maximum transmission
distance
Connection method
CP1W-CIF01
One RS-232C port
15 m
Connector (D-sub, 9-pin female)
CP1W-CIF11
One RS-422A/485 port
50 m (See note.)
Terminal block (using ferrules)
CP1W-CIF12
One RS-422A/485 port
500 m
Terminal block (using ferrules)
Communications
cables
Low-current cables
PLC power supply
and general control
circuit wiring
Power lines
300 mm min.
Ground to 100
Ω
or less.
Control cables
Power cables
300 mm min.
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......