111
Mounting
Section 3-3
Use I/O Connecting Cable when connecting CP-seriess Expansion Units and
Expansion I/O Units at the same time as CJ-series Special I/O Units or CPU
Bus Units.
Wiring Ducts
Whenever possible, route I/O wiring through wiring ducts. Install the duct so
that it is easy to wire from the I/O Units through the duct. It is handy to have
the duct at the same height as the Racks.
Note
Tighten terminal block screws and cable screws to the following torque.
M4: 1.2 N·m
M3: 0.5 N·m
CP1W-CN811
I/O Connecting Cable
CP1H CPU Unit
DIN Track
20 mm min.
20 mm min.
40 mm
30 mm
30 mm
81.6 to 89.0 mm
Duct
Unit
Duct
DIN Track
Duct
CPU
Rack
Mounting
bracket
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......