154
I/O Area and I/O Allocations
Section 4-2
4-2-3
Allocations to CP1H Y CPU Units (12 Inputs/8 Outputs)
Bits are allocated to a Y CPU Unit in discontinuous positions, as shown in the
figure below, due to allocations for the pulse I/O terminals.
Input Bit Allocations
As shown above, a total of 12 input bits in CIO 0 and CIO 1 are allocated for
the Y CPU Unit. Unused bits in CIO 0 and CIO 1 are always cleared and can-
not be used as work bits.
Output Bit Allocations
As shown above, a total of 8 output bits in CIO 100 and CIO 101 are allocated
for the Y CPU Unit. Unused bits can be used as work bits.
4-2-4
Allocations to CP1W Expansion Units and Expansion I/O Units
Expansion I/O Units
There are Expansion I/O Units for expanding inputs, for expanding outputs,
and for expanding both input and outputs. I/O bits starting from bit 00 in the
next word after the word allocated to the previous Expansion Unit, Expansion
Inputs
Outputs
CIO 0.00, CIO 0.01, CIO 0.04,
CIO 0.05, CIO 0.10, CIO 0.11,
CIO 1.00 to CIO 1.05
CIO 100.04 to CIO 100.07
CIO 101.00 to CIO 101.03
12 inputs
8 outputs
CPU Unit
CIO 2.00 on
CIO 102.00 on
Expansion Unit
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
CIO 0
CIO 1
CIO 2
CIO 3
CIO 4
CIO 5
CIO 6
CIO 7
12 input bits allocated to Y CPU Unit
Input bits allocated to CP-series Expansion I/O Units
Allocation area for 8-input Unit
Allocation area for 12-input or 24-input Unit
Do not use.
Do not use.
Do not use.
Do not use.
Do not use.
15 14 13
12 11 10 09 08 07
06 05 04
03 02 01 00
CIO 100
CIO 101
CIO 102
CIO 103
CIO 104
CIO 105
CIO 106
CIO 107
8 outputs allocated to Y CPU Unit
Allocation area for 8-output or 16-output Unit
Outputs allocated to
CP-series Expansion I/O Units
Can be used as work bits.
Can be used as work bits.
Can be used as work bits.
Do not use.
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......