181
Task Flags
Section 4-17
4-17 Task Flags
Task Flags range from TK00 to TK31 and correspond to cyclic tasks 0 to 31. A
Task Flag will be ON when the corresponding cyclic task is in executable
(RUN) status and OFF when the cyclic task hasn’t been executed (INI) or is in
standby (WAIT) status.
Note
These flags indicate the status of cyclic tasks only, they do not reflect the sta-
tus of interrupt tasks.
Task Flag Initialization
The Task Flags will be cleared in the following cases, regardless of the status
of the IOM Hold Bit.
1.
When the operating mode is changed from PROGRAM mode to
RUN/MONITOR mode or vice-versa
2.
When the power is cycled.
Forcing Bit Status
The Task Flags
cannot
be force-set and force-reset.
4-18 Condition Flags
These flags include the Arithmetic Flags, such as the Error Flag and Equals
Flag, which indicate the results of instruction execution.
The Condition Flags are specified with symbols, such as P_CY and P_ER,
rather than addresses. The status of these flags reflects the results of instruc-
tion execution, but the flags are read-only; they cannot be written directly from
instructions or the CX-Programmer.
Note
The CX-Programmer treats condition flags as global symbols beginning with
P_.
All Condition Flags are cleared when the program switches tasks, so the sta-
tus of the ER and AER flags are maintained only in the task in which the error
occurred.
Forcing Bit Status
The Condition Flags
cannot
be force-set and force-reset.
Summary of the Condition
Flags
The following table summarizes the functions of the Condition Flags, although
the functions of these flags will vary slightly from instruction to instruction.
Refer to the description of the instruction for complete details on the operation
of the Condition Flags for a particular instruction.
Name
Symbol
Function
Error Flag
P_ER
Turned ON when the operand data in an instruction is incorrect (an
instruction processing error) to indicate that an instruction ended
because of an error.
When the PLC Setup is set to stop operation for an instruction error
(Instruction Error Operation), program execution will be stopped and
the Instruction Processing Error Flag (A29508) will be turned ON
when the Error Flag is turned ON.
Access Error Flag
P_AER
Turned ON when an Illegal Access Error occurs. The Illegal Access
Error indicates that an instruction attempted to access an area of
memory that should not be accessed.
When the PLC Setup is set to stop operation for an instruction error
(Instruction Error Operation), program execution will be stopped and
the Instruction Processing Error Flag (A429510) will be turned ON
when the Access Error Flag is turned ON.
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......