465
Temperature Sensor Units
Section 7-5
Converted Analog Data
“m” is the last input word allocated to the CPU Unit, Expansion I/O Unit, or
Expansion Unit connected immediately before the Temperature Sensor Unit.
Startup Operation
After power is turned ON, approximately 1 s is required for the first conversion
data to be stored in the input word. During that period, the data will be 7FFE.
Therefore, create a program as shown below, so that the ladder can start to
operate with valid conversion data in input words.
Programming Example
The following programming example shows how to store the input data of
CP1W-TS003 (4 inputs) in D0 to D3, and W10.00~W10.13 turns ON at the
time of open-circuit detection.
DIP Switch Setting
SW1
OFF
K
SW2
OFF
°C
SW3
NC
SW4
OFF
Thermocouple
SW5
ON
Analog
SW6
ON
1 to 5V/4 to 20mA
m+3
Converted analog data from input 2
m+4
Converted analog data from input 3
(P_EQ)
1000.00
2
#7FFE
P_On
CMP(020)
Always ON
Temperature input data
output word
Initialization
Completed Flag
None
CP1W-TS003
Temperature Sensor Unit
Temperature unit setting: OFF(ºC)
Input range setting
Input 0: Thermocouple K(CIO2)
Input 1: Thermocouple K(CIO3)
Input 2: Thermocouple K(CIO4)
Input 3: Analog input 1 to 5V(CIO5)
CP1H
Input word
addresses
Output word
addresses
CIO 0
CIO 1
CIO 100
CIO 101
CIO 2
CIO 3
CIO 4
CIO 5
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......