624
Replacing User-serviceable Parts
Section 12-2
Note
1.
When replacing a CPU Unit, be sure that not only the user program but
also all other data required for operation is transferred to or set in the new
CPU Unit before starting operation, including DM Area and HR Area set-
tings. If data area and other data are not correct for the user program, un-
expected accidents may occur.
2.
Be sure to include the routing tables, Controller Link Unit data link tables,
network parameters, and other CPU Bus Unit data, which are stored as pa-
rameters in the CPU Unit. Refer to the CPU Bus Unit and Special I/O Unit
operation manuals for details on the data required by each Unit.
12-2 Replacing User-serviceable Parts
The following parts should be replaced periodically as preventative mainte-
nance. The procedures for replacing these parts are described later in this
section.
• Battery (backup for the CPU Unit’s internal clock and RAM)
Battery Functions
The battery maintains the internal clock and the following data in the retained
regions of I/O memory while the main power supply is OFF.
If the battery is not installed or battery voltage drops too low, the internal clock
will stop and the data in RAM will be lost when the main power supply goes
OFF.
Battery Service Life and
Replacement Period
At 25
°
C, the maximum service life for batteries is five years whether or not
power is supplied to the CPU Unit while the battery is installed. The battery’s
lifetime will be shorter when it is used at higher temperatures.
The following table shows the approximate minimum lifetimes and typical life-
times for the backup battery (total time with power not supplied).
Note
The minimum lifetime is the memory backup time at an ambient temperature
of 55
°
C. The typical lifetime is the memory backup time at an ambient temper-
ature of 25
°
C.
Model
Approx.
maximum lifetime
Approx. minimum
lifetime (See note.)
Typical lifetime
(See note.)
CP1H-X/XA40DR-A
CP1H-X/XA40DT(1)-D
CP1H-Y20DR-D
5 years
13,000 hours
(approx. 1.5 years)
43,000 hours
(approx. 5 years)
Memory Backup Time
Ambient temperature
This graphic is for reference only.
5 yr
4 yr
3 yr
2 yr
1 yr
CP1H CPU Unit
25
°
C
40
°
C
55
°
C
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......