![background image](http://html1.mh-extra.com/html/omron/sysmac-cp1h/sysmac-cp1h_operation-manual_741321159.webp)
125
Wiring CP1H CPU Units
Section 3-4
3-4-3
Wiring Safety and Noise Controls
I/O Signal Wiring
Whenever possible, place I/O signal lines and power lines in separate ducts or
conduits both inside and outside of the control panel.
If the I/O wiring and power wiring must be routed in the same duct, use
shielded cables and connect the shields to the GR terminal to reduce noise.
Inductive Loads
When an inductive load is connected to an I/O Unit, connect a surge suppres-
sor or diode in parallel with the load as shown below.
Note
Use surge suppressors and diodes with the following specifications.
Noise from External
Wiring
Take the following points into account when externally wiring I/O, power sup-
ply, and power lines.
• When multi-conductor signal cable is being used, avoid combining I/O
wires and other control wires in the same cable.
• If wiring racks are parallel, allow at least 300 mm between the Racks.
(1)
(2)
(1)
(2)
(1)
(2)
Suspended duct
In-floor duct
(1) = I/O cables
(2) = Power cables
Conduits
L
IN
COM
OUT
COM
OUT
COM
L
+
Diode
DC input
Relay output
Surge suppressor
Relay output or
transistor output
Diode
Surge Suppressor Specifications
Resistance: 50
Ω
Capacitance: 0.47
µ
F
Voltage: 200
V
Diode Specifications
Breakdown voltage:
3 times load voltage min.
Mean rectification current: 1 A
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......