166
Auxiliary Area (A)
Section 4-11
area). These words cannot be specified as instruction operands in the user
program.
Precautions
When a Holding Area bit is used in a KEEP(011) instruction, never use a nor-
mally closed condition for the reset input if the input device uses an AC power
supply. When the power supply goes OFF or is temporarily interrupted, the
input will go OFF before the PLC’s internal power supply and the Holding Area
bit will be reset.
Instead, use a configuration like the one shown below.
There are no restrictions in the order of using bit address or in the number of
N.C. or N.O. conditions that can be programmed.
4-11 Auxiliary Area (A)
The Auxiliary Area contains 960 words with addresses ranging from A0 to
A959). These words are preassigned as flags and control bits to monitor and
control operation.
A0 through A447 are read-only, but A448 through A959 can be read or written
from the program or the CX-Programmer.
Refer to
Appendix C Auxiliary Area Allocations by Function
and
Auxiliary Area Allocations by Address
for Auxiliary Area functions.
Forcing Bit Status
Read/write bits in the Auxiliary Area cannot be force-set and force-reset con-
tinuously.
4-12 TR (Temporary Relay) Area
The TR Area contains 16 bits with addresses ranging from TR0 to TR15.
These temporarily store the ON/OFF status of an instruction block for branch-
ing and are used only with mnemonics. TR bits are useful when there are sev-
eral output branches and interlocks cannot be used.
The TR bits can be used as many times as required and in any order required
as long as the same TR bit is not used twice in the same instruction block.
TR bits can be used only with the OUT and LD instructions. OUT instructions
(OUT TR0 to OUT TR15) store the ON OFF status of a branch point and LD
instructions recall the stored ON OFF status of the branch point.
Forcing Bit Status
TR bits cannot be changed from the CX-Programmer.
Input
Unit
Set input
Reset input
H1.00
Input
Unit
Set input
Reset input
H1.00
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......