118
Wiring CP1H CPU Units
Section 3-4
DIN Track
Mount the DIN Track in the control panel with screws in at least three places.
• DIN Track: PFP-50N (50 cm), PFP-100N (100 cm), or PFP-100N2
(100 cm)
Secure the DIN Track to the control panel using M4 screws separated by
210 mm (6 holes). The tightening torque is 1.2 N·m.
3-4
Wiring CP1H CPU Units
Note
(1) Do not remove the protective label from the top of the Unit until wiring has
been completed. This label prevents wire strands and other foreign mat-
ter from entering the Unit during wiring procedures.
(2) Remove the label after the completion of wiring to ensure proper heat dis-
sipation.
15
10
4.5
25
25
25
10
25
15
1000
1000 (500)
(See note.)
PFP-100N2
PFP-100N/50N
15
10
4.5
25
25
25
10
25
15 (5)
(See note.)
1
16
1.5
1
29.2
24
27
30
±
0.3
7.3
±
0.15
35
±
0.3
27
±
0.15
28.25
×
4.5 oblong holes
Note:
PFP-50N dimensions are given in parentheses.
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......