383
Failure Diagnosis Functions
Section 6-7
6-7
Failure Diagnosis Functions
This section introduces the following functions.
• Failure Alarm Instructions: FAL(006) and FALS(007)
• Failure Point Detection: FPD(269)
• Output OFF Bit
6-7-1
Failure Alarm Instructions: FAL(006) and FALS(007)
The FAL(006) and FALS(007) instructions generate user-defined errors.
FAL(006) generates a non-fatal error that allows program execution to con-
tinue and FALS(007) generates a fatal error that stops program execution.
When the user-defined error conditions (i.e., the execution conditions for
FAL(006) or FAL(007)) are met, the instruction will be executed and the follow-
ing processing will be performed.
1,2,3...
1.
The FAL Error Flag (A402.15) or FALS Error Flag (A401.06) is turned ON.
2.
The corresponding error code is written to A400.
3.
The error code and time of occurrence are stored in the Error Log.
4.
The error indicator on the front of the CPU Unit will flash or light.
5.
If FAL(006) has been executed, the CPU Unit will continue operating.
If FALS(007) has been executed, the CPU Unit will stop operating. (Pro-
gram execution will stop.)
Operation of FAL(006)
When execution condition A goes ON, an error with FAL number 002 is gener-
ated, A402.15 (FAL Error Flag) is turned ON, and A360.02 (FAL Number 002
Flag) is turned ON. Program execution continues.
Errors generated by FAL(006) can be cleared by executing FAL(006) with FAL
number 00 or performing the error read/clear operation from the CX-Program-
mer.
Operation of FALS(007)
When execution condition B goes ON, an error with FALS number 003 is gen-
erated, and A401.06 (FALS Error Flag) is turned ON. Program execution is
stopped.
Errors generated by FAL(006) can be cleared by eliminating the cause of the
error and performing the error read/clear operation from the CX-Programmer.
A
FAL
002
#0000
B
FALS
003
#0000
Summary of Contents for Sysmac CP1H
Page 2: ......
Page 3: ...CP1H X40D CP1H XA40D CP1H Y20DT D CP1H CPU Unit Operation Manual Revised October 2014...
Page 4: ...iv...
Page 10: ...x...
Page 18: ...xviii...
Page 22: ...xxii...
Page 34: ...xxxiv Conformance to EC Directives 6...
Page 76: ...42 Function Blocks Section 1 5...
Page 176: ...142 CP series Expansion I O Unit Wiring Section 3 6...
Page 372: ...338 Analog I O XA CPU Units Section 5 5...
Page 578: ...544 Trouble Shooting Section 8 7...
Page 622: ...588 Sample Application Section 9 12 Network Settings Network Tab Network Settings Driver Tab...
Page 668: ...634 Standard Models Appendix A...
Page 744: ...710 Auxiliary Area Allocations by Address Appendix D...
Page 771: ...737 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Page 772: ...738 Connections to Serial Communications Option Boards Appendix F...
Page 800: ...766 Specifications for External Power Supply Expansion Appendix H...
Page 806: ...772 Index W Work Area 165 work bits 165 work words 165 write protection 379...
Page 808: ...774 Revision History...
Page 809: ......