136
Commands and Responses for Controller Link Units
Section 6-5
Status (response): The data link status of each mode is returned as shown
in the following diagram. It is the same as the data link status in the PLC.
(Refer to page 102.)
If 0000 Hex is specified as the command type (or it is omitted), only the
32 bytes for nodes 1 to 32 will be returned.
1.
The data link status is not refreshed while the data links are inactive.
2.
Nodes which are not active in the network or participating in the data links
will generate communications errors.
3.
Any node which is not active in the network retains the status that existed
immediately prior to the generation of the communications error.
4.
Only the PLC operation status and PLC error status will be refreshed for
nodes that are not participating in a data link that is active in the network.
6-5-8
CONNECTION DATA READ
Reads in order of connection (descending direction) the node addresses of
Controller Link Units connected in a ring. This command can only be used in
token-ring mode, for Optical Ring Controller Link Units (H-PCF cable or GI
cable).
Command Block
Response Block
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Byte 1
Byte 2
Byte 3
Bit
Byte 62
Node #1
Node #2
Node #3
Node #62
Data link status for each node
PLC status
0: Inactive (user program not running)
1: Active (user program running)
Communications error (data link reception)
0: Normal
1: Error
PLC's CPU Unit error
0: Normal
1: Error
Data link participation
0: Not in data link or data link inactive
1: In data link
Offset error
0: Normal
1: Error
Error: Offset exceeds number of send words.
Insufficient (short) receive area
0: Sufficient
1: Insufficient
Insufficient: Receive area is smaller than send area.
Excess data is truncated; other data is received.
Remaining receive area
0: Not remaining
1: Remaining
Remaining: Receive area is larger than send area.
Data is received and remaining words are cleared.
−
Command
format
04
06
Beginning node to read
Number of nodes read
Command
code
Node addresses read
06
04
Response
code
Minute
Day
Year
Second
Hour
Month
Time connection data created
Number of nodes read
Node address
Node address
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...