280
CS-series Optical Bus Controller Link Units
Appendix C
Communications Specifications
Optical Ring System
Note 1.
The maximum distance between nodes depends on the connector and cable processing methods.
2.
The CS-series PLCs do not have an LR area, but CIO 1000 through CIO 1199 are used automatically
in place of LR 000 to LR 199.
Items
Specifications
Communications method
N:N token bus
Code Manchester
code
Modulation Baseband
code
Synchronization
Flag synchronization (conforms to HDLC frames)
Transmission path form
Daisy-chain
Baud rate
2 Mbps
Maximum transmission dis-
tance
20 km
Maximum distance
between nodes
Crimp cut: 800 m
Adhesive: 1 km (See note 1.)
Media
H-PCF cable (optical two-core cable)
Node connection method
Connected via a special (full-lock connector) connector. (A half-lock connector can also be
used.)
Maximum number of nodes 32 nodes
Communications functions
Data links and message service
Number of data link words
Transmission area per node:
1,000 words (2,000 bytes) max.
Data link area in one PLC (CS-series PLC) (send/receive):
12,000 words (24,000 bytes) max.
Number of data link words in one network (total transmission):
32,000 words (64,000 bytes) max.
Data link areas
Bit areas (IR, AR, LR (See note 2.), CIO), data memory (DM), and extended data memory
(EM)
Message length
2,012 bytes max. (including the header)
RAS functions
Polling node backup function
Self-diagnosis function (hardware checking at startup)
Echoback test and broadcast test (using the FINS command)
Watchdog timer
Error log function
Node bias function
Error control
Manchester code check
CRC check (CCITT X
16
+ X
12
+ X
5
+ 1)
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...