82
Setting Data Links
Section 5-2
set in the data link startup node. Data links will not be started unless the
settings are correct.
5-2-2
Manual Setting
Transfer the data link tables that were created on the Controller Link Support
Software (Ver. 2.00 or later) or CX-Net (in CX-Programmer) to the Controller
Link Unit or the Controller Link Support Board (for IBM PC/AT or compatible
computers).
The data link tables are transferred from a computer running the Controller
Link Support Software (Ver. 2.00 or later). The computer can either be a node
in the network or a computer attached as a Programming Device.
Transferring from a Programming Device
Note
1.
When transferring data link tables to a CS-series PLC, set pin 1 of the DIP
switch on the CPU Unit to “OFF.” Otherwise, data link tables cannot be writ-
ten normally.
2.
When transferring the data link tables to a CVM1 or CV-series PLC, set the
System Protect Keyswitch on the CPU Unit to “NORMAL.” Otherwise, data
link tables cannot be written normally.
3.
The Controller Link Support Software (Ver. 2.00 or later) can be integrated
into the SYSMAC Support Software. Refer to the Controller Link Support
Software Operation Manual (W308) for details.
Transferring from a Computer Node
Nodes
Controller
Link Unit
CPU Unit
+
Nodes
Controller
Link Unit
CPU Unit
CVM1 and CV-series PLCs
Transmissions
Setting data link tables
IBM PC/AT or
compatible
Controller Link
Support Soft
ware (Ver. 2.00
or later) or CX-
Net (in CX-Pro-
grammer)
CS-series PLCs
• • •
Setting data link tables
IBM PC/AT or compatible
computer
Controller Link
Support Board
Controller Link
Support Software
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...